Manual
nEnglish translation of German original
Authorised electrician
Important safety instructions
These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all
times.
blueplanet gridsave 92.0 TL3-S
blueplanet gridsave 110 TL3-S
blueplanet gridsave 137 TL3-S
M; L; XL

Advertisement

Table of Contents
loading

Summary of Contents for Kaco blueplanet gridsave 92.0 TL3-S

  • Page 1 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S M; L; XL Manual nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
  • Page 2 | Legal provisions Manual Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication of this document, in whole or in part, is subject to the written consent of KACO new energy GmbH. KACO warranty For current warranty conditions contact your system integrator.
  • Page 3: Table Of Contents

    7.7 Establishing equipotential bonding ....26 7.8 Connecting the interfaces......26 7.9 Sealing the connection area ......29 8 Commissioning............ 30 8.1 Requirements ..........30 8.2 Start-up options..........30 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 4: General Information

    Country-specific certificates Module-specific certification Layout of Instructions 1.3.1 Symbols used General hazard Fire and risk of explosion Electrical voltage Risk of burns Earthing - ground conductor Page 4 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 5: Identification

    Cert. to CSA C22.2 No. 107.1 & CAN/CSA Std. C22.2 No. 62019-1 CAN/CSA Std. C22.2 No. 62109-2 WJDA Fig. 1: Name plate – Disposal information – Certification marking, CE marking. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 5 TL3-S...
  • Page 6: Warnings On The Device

    – Education concerning the installation and start-up of electrical devices and systems. – Knowledge of applicable standards and directives. – Knowledge and adherence to this document with all safety notices. Page 6 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 7: Safety

    The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap- proved or for which it has been released by KACO new energy and the grid operator. Nevertheless, improper use may cause lethal hazards for the operator or third parties, or may result in damage to the device and other property.
  • Page 8: Protection Features

    – Approval from KACO new energy is required for a parallel DC circuit with more than 2 bidirectional feed-in inverters. Any other or additional use is not considered proper or intended use and can lead to an annulment of the product guar- antee.
  • Page 9: Description Of The Device

    The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. Energy management system/power management system blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 9 TL3-S...
  • Page 10 It is possible to establish a connection to the webserver integrated into the device by connecting a USB-WiFi stick. In addi- tion to commissioning, service information and firmware updates, more extensive configurations are also possible via the web interface. Page 10 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 11: System Layout

    Bidirectional feed-in inverter The connection from the battery unit is carried out on the device's DC connection. Line protection Safety fuse or circuit breaker. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 11 TL3-S...
  • Page 12: Technical Data

    Display LED´s LEDs For country setting UD and IL the working range can be increased to 1450 V.See table : Configuration via web user interface [} Page 57] Page 12 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 13: Environmental Data

    > 500 m coast Pollution level inside the en- 2 (reduced by IP 66 Housing) closure Pollution level outside the en- closure Ambient temperature -20-+60 °C blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 13 TL3-S...
  • Page 14 OD II KL / BLUEPLANET GS OD IIPL / BLUEPLANET GS GS 92.0 TL3 M1 WM OD IIGX 110 TL3 M1 WM OD IIKX 137 TL3-S B1 WM OD IIPX Page 14 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 15: Transportation And Delivery

    Contour screw head head Tightening torque Outer hexagon Internal hexagon Spanner size or number Torx Slot Outer contour Tab. 1: Legend Description Tool abbreviation Fig. 6: Presentation format blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 15 TL3-S...
  • Page 16: Assembly And Preparation

    – Close to the ground, accessible from the front and sides without requiring additional resources. – In outdoor areas, KACO new energy recommends protecting the device from direct weather exposure and sunlight. This should be carried out by means of constructional measures (e.g. wind breaks) in order to reduce thermal heating of the components, premature derating and more extensive wear of the fans.
  • Page 17: Unpacking The Device

    ↻ The device is transported to the installation location. 1. Remove the plastic band from the pallet and packaging. 2. Pull the clamp off the packaging. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 17 TL3-S...
  • Page 18: Fastening The Mount

    3. Fix the mount to the wall using suitable mounting fixtures from the mounting kit. . NOTE: Make sure that the mount is oriented correctly. Page 18 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 19: Installing And Securing The Device

    3. Insert the screw provided into the lug of the mount and [ T30 / 2 Nm ] ( [See figure 11 [} Page 18]). ð Device is installed. Proceed with the electrical installation. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 19 TL3-S...
  • Page 20 2. Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installa- tion. 3. Immediately remove any moisture from the housing. Page 20 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 21: Installation

    Specification of the DC fuse (F1): • 250Adc nominal current • Nominal voltage (DC) > max. battery voltage • Breaking capacity: 30kA Use of e.g. Bussmann EATON PV-250A-2XL-3BU-15 (1500Vdc). blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 21 TL3-S...
  • Page 22 RS485 terminal cable cross-section 0,25 - 1,5 mm² Cable diameter for cable fitting (3x) 5 - 10 mm Torque for cable fitting 1,5 (M16) Nm Ethernet connection type RJ45 Page 22 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 23: Connecting The Device To The Power Grid

    Otherwise, the aluminium may be destroyed by the copper busbars in the presence of electrolytes (e.g. con- densate). If the connection is made in a TN-C grid, connect the PEN grounding cable to the ground earthing point. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 23 TL3-S...
  • Page 24: Connecting The Battery To The Device

    7. Check secure fit of all connected cables. 8. Ensure that the polarity is correct. Fig. 22: DC connection XL version 9. Tighten cable fittings [ W_46 / 10 Nm ]. Page 24 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 25: Inserting The Overvoltage Protection

    3 AC surge protection module 3. Remove SPD monitoring jumper for automatic monitoring. (4 slots) ð Proceed with the installation of the device. 4 SPD monitoring jumper blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 25 TL3-S...
  • Page 26: Establishing Equipotential Bonding

    2. Earth yourself before touching a component by touching a grounded object. All interfaces are located on the communication circuit board (HMI board) inside the housing. Page 26 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 27 3. Pass the connection cable through the cover of the cable fitting and the sealing insert. 4. Insert the sealing insert into the cable fitting. 5. Feed the connection cables into the connection area. ð Ethernet cable inserted. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 27 TL3-S...
  • Page 28 1. Please note the corresponding application note under Downloads and Videos in the category PV ac- cessories - powador-protect. 2. When using devices from other manufacturers or in combination with KACO inverters, interface switches as a minimum must be used for shutting down devices from other manufacturers.
  • Page 29: Sealing The Connection Area

    2. Secure the housing cover (1) by tightening all 6 screws (2) in a diagonally oppos- ite sequence [ T_25/ 5 Nm]. ð The device has been mounted and installed. ð Put the device into operation. Fig. 31: Close the housing cover blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 29 TL3-S...
  • Page 30: Commissioning

    – The installation technician can start up the device with the aid of the installation wizard as described at option 1. The device can be addressed using its host name. Page 30 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 31 Tab. 2: Start-up variants for individual devices or system segments 8.2.1 Start-up via WIFI The following figure provides an example of the structure of a KACO device with string combiner (SC) and mobile devices connected without cables. Application The planned network infrastructure or AC-coupling is not yet in place or has not been completed.
  • Page 32 ð Once the parameters have been adopted and the device has been restarted, the device is put into operation. 8.2.4 Starting up a network The following illustration provides an example of the structure of a KACO unit with a string collector (SC) and an external network connection. MODBUS TCP /...
  • Page 33 RFC229, host names must not contain any "." dots. For local host names, only characters in the range [a-z], [A-Z] and the minus character are permitted. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 33...
  • Page 34: Configuration And Operation

    ð The Forward button jumps to the next installation step. It is only possible to configure the grid parameters with DC voltage. The further parameters can also be con- figured with a present AC voltage. Page 34 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 35 It is preferable to install this on a plant component. It is also possible to select an NTP server localized on the internet provided the device has direct access to the internet. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 35...
  • Page 36: Signal Elements

    No LED is lit. Error on the device or AC/DC source Fault The red "Fault" LED is illuminated. Fault in the AC/DC source Conditional special cases: Page 36 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 37: User Interface

    NOTE The values for the condition of the battery connected are transmitted from the EMS directly. We cannot provide any guarantee that these values are correct. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 37 TL3-S...
  • Page 38 Basic layout - 2nd tab Displays AC and DC voltages Basic layout - 3rd tab Current measurement values with export function Tab. 3: Description of the areas Page 38 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 39 Enables selection of connected interfaces. Enables selection of devices connected at the interface. Enables selection of functions in relation to the parameter selected. Tab. 4: Description of the areas blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 39 TL3-S...
  • Page 40: Menu Structure

    ð The web interface shows the selected data. Weekly view NOTE: Displays the recorded operating data graphically. F Select a week. ð The web interface shows the selected data. Page 40 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 41 NOTE: Opportunity to activate standard protective shutdown Trip with intentional 1. If necessary, activate delayed trip-off. delay 2. Activate optional password protection. Password protection 3. Confirm the action field. Status blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 41 TL3-S...
  • Page 42 45.0 – 67.5 [Hz] / 51.5 [Hz] / 0.01 Trip overfrequency time level 2 – 5 0 – 10000000 [ms] / 100 / Password protection Status Page 42 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 43 – 5 100 – 125 [% U 114.8 [% U Trip overvoltage time level 2 up to 5 0 – 120000 [ms] / Password protection Status blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 43 TL3-S...
  • Page 44 ROCOF threshold stage F Define time value for ROCOF. 1 time 0.10 – 5.00 [ s] / ROCOF threshold stage 2 time 0.10 – 5.00 [ s] / Page 44 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 45 This percentage relates to the nominal frequency. 1 – 65534 [%/min] / 1. Activate optional password protection. 65534 / 2. Confirm the action field. Password protection Status blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 45 TL3-S...
  • Page 46 1. Set waiting time after grid failure. failure 2. Activate optional password protection. 1000 – 1800000 3. Confirm the action field. [ms] / 60000 / 1000 Password protection Status Page 46 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 47 2. Maximum change in the active power in the event of a change to crease underexcited mode. 1 – 65534 [% Slim / min] / 65534 [% Slim / min] / blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 47 TL3-S...
  • Page 48 2. Determine the gradient for loading in the event of underfrequency. loading 0 – 200 (%/Hz) ; 40 (%/Hz) Gradient in the event of underfrequency - loading 0 – 200 (%/Hz) ; 40 (%/Hz) Page 48 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 49 Operation mode Off | On Off: Deactivates dynamic grid support using dynamic reactive current. Dynamic grid support remains active on account of immunity to inter- ference. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 49 TL3-S...
  • Page 50 1. Specify voltage for 1st, 5th ... node as a percentage of the maximum voltage. 80.0 – 125.0 [%Unom] / 112 / 2. Activate optional password protection. 3. Confirm the action field. Password protection Status Page 50 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 51 0 – 100 [% Slim] / 0 [% Slim] / Underexcited | over- F Select the type of phase shift. excited NOTE: Underexcited relates to inductive load, overexcited relates to capacitive load. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 51 TL3-S...
  • Page 52 NOTE: Overexcited relates to a capacitive load, underexcited relates to Password protection an inductive load. Status 1. Activate optional password protection. 2. Confirm the action field. Page 52 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 53 0 – 60000 [ms] / 30000 [ms] / 1000 [ms] F Set the intentional delay for the start of the Q(U) function. Dead time 0 -10,000 [ms] / [ms] / blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 53 TL3-S...
  • Page 54 1st or last node is used each time. FRT (Fault Ride NOTE: The device supports dynamic grid stabilization (Fault Ride- Through) Through).NOTE:  More detailed information at: [See sec- tion 10.3} Page 76] Page 54 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 55 F Set voltage range for the active control process. voltage deactivation 45.0 – 125.0 [% Unom] 0.1 & Maximum operating voltage deactivation 45.0 – 125.0 [% Unom] Password protection Status blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 55 TL3-S...
  • Page 56 Off: The device does not check whether a Powador-protect is integrated into the PV plant. Page 56 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 57 F Set the port at which the web server can be reached. HTTP Port HTTPS Port 1. Set the secured port at which the web server can be reached. 2. Confirm the action field. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 57 TL3-S...
  • Page 58 Power Unit state NOTE: View the status of the power unit Requested state Connection status: see in the "SunSpec Information Model Reference KACO" document under Model- 64201 "enum16" as well as in the Integ- Mode: Off, Standby, ration Manual. Connected Column: Local The unit reacts to the local values specified via the web interface.
  • Page 59 Q Setpoint NOTE: Define Q Setpoint Reactive power set- F Set reactive power Q to a fixed value point 0 - 100 [% VarMax] / 0 [% VarMax]/ blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 59 TL3-S...
  • Page 60 NOTE: Setting and time until memory is overwritten: 1 min – 5 days; 5 [minutes] / min – 4.5 years; 10 min – 9 years; 15 min – 14 years. Page 60 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 61 NOTE: The following is specific to KACO: Following initial start-up, it is necessary to Change password Restart the Device NOTE: Transfer safety-related parameters to a storage medium. F If necessary, re-start the device. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 61 TL3-S...
  • Page 62: Monitoring The Device

    Manual NOTE With regard to the selection of country settings, KACO new energy attests: 1. that the relevant certificates are only valid if the corresponding country settings have been selected. 2. that all configured grid parameters must be configured in accordance with the requirements of the grid op- erators.
  • Page 63: Access Via Modbus

    ↻ Pay attention to signal elements (LEDs) and statuses during the process. ↻ Note the description of the LED states during the process. [See section 9.2} Page 36] 1. Load the firmware from the KACO website onto a FAT32-formatted USB stick. 2. Insert the USB stick into the USB port of the device.
  • Page 64: Specifications

    U [V] Fig. 46: P-Q operating range for bp gridsave 92.0 TL3-S Fig. 47: Apparent power subject to the grid voltage bp grid- save 92.0 TL3-S Page 64 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 65 Q const. and the Q(U) mode. The maximum possible active power that can be fed in is reduced in line with the P-Q operating range when the maximum grid power is reached. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 65...
  • Page 66 The positive phase sequence voltage is used to calculate the reactive power target value for three-phase devices. Page 66 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 67 NOTE: The gradient is overlaid with the settling time. 1 – 65,534 [% S min] / 65,534 [% S min] / blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 67 TL3-S...
  • Page 68 100%. The power values of the nodes must increase continu- 0V - Max. voltage in ously. continuous operation Note: Storage inverters only for feed-in operation Page 68 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 69 Once the [ms] / dead time has expired, the control circuit is no longer subject to a delay and the set setting time determines the transient behaviour. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 69 TL3-S...
  • Page 70: Active Power Regulation

    In all of the control methods described below the specified target value at the inverter's connection terminals is adjusted using a stationary deviation of the reactive power of maximum 2% S Page 70 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 71 F Activate the control process. Off | On Off: Deactivates dynamic grid support using dynamic reactive current. Dynamic grid support remains active on account of immunity to inter- ference. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 71 TL3-S...
  • Page 72 Power 0.0 – 100.0 [% P 100.0 [% P Voltage 80.0 – 126.0 [% 112.0 [% Page 72 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 73 Fig. 61: Example behaviour with hysteresis (mode 1) Fig. 62: Example behaviour without hysteresis (mode 2) At the time of activation, the inverter is in charging mode at 20% charging capacity. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 73 TL3-S...
  • Page 74 45 – 50 [Hz] 0.01 to guarantee a linear power adjustment and reach the maximum feed-in [Hz] power if the frequency drops to the minimum configured frequency. Page 74 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 75 / sible fluctuation in the available power or the target value, but at no time increases above the absolute power limit. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 75 TL3-S...
  • Page 76: Frt

    For VDE AR-N 4105:2018 and VDE AR-N 4110:2018 an immunity to over voltage up to 125 % U is required. In the com- pliant country settings (DE-NS2018 and DE-4110) U is configured to 662 V DCmin Page 76 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 77 (2) and (3). Dynamic grid support using fast feeding of residual current is then deactivated after a configured minimum support time, usually 5 s. Fig. 68: Formula no. 4 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 77 TL3-S...
  • Page 78 (2) and (4). Can be configured inde- pendently for drops and spikes. Constant k positive se- quence swell k 0 – 10 / Page 78 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 79: Other Grid-Supporting Functions That Are Effective In The Case Of Active Power

    Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Because KACO devices have the full P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power because an apparent power reserve is not available.
  • Page 80 Time / s Fig. 70: Power gradient according to sample parameters and calculation The following formulae are used to calculate the Q filter parameter and cos ϕ gradient: Page 80 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 81: Advanced Islanding Detection

    Enhanced island detection method The new method by KACO new energy, enhanced island detection, employs a strategy to reliably detect island formation that is based on the characteristic differences between an interconnected grid and an islanded grid, thus ensuring reliable fast detection and prevention of false tripping.
  • Page 82 100 ms. With stage 2 active, the device has switched off and the set reconnection con- ditions shall apply. Page 82 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 83: Maintenance And Troubleshooting

    ü The cleaning intervals must be adapted to match the ambient conditions of the installation location. 1. In sandy environments, we recommend cleaning the heat sinks and fans every quarter. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 83...
  • Page 84: Replacing The Fan

    3. Set the cover to one side. Fig. 75: Remove the cover ð Proceed with the cleaning or removal of the fans. 1 Cover 2 Screw for fixing 3 Mounting clips 4 Fan Page 84 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 85 4. Unlock the power supply to the connector. 3 Board 5. Detach the fan grille from the housing. 6. Remove dust and dirt particles from the housing. ð Install the replacement fan. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 85 TL3-S...
  • Page 86: Shutting Down For Maintenance / Troubleshooting

    [ W35] against it [ W17 / 5 Nm]. 3. DC fuse replaced. Continue connecting the battery. Fig. 80: Replace DC fuse Page 86 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 87: Faults

    Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. 1. If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service.
  • Page 88: Messages

    The overview of all existing status & fault messages, can be found in the associated integration manual, which you can obtain from KACO sales team (pv-projects.kaco.de@siemens.com). Page 88 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 89: Decommissioning And Dismantling

    1. Undo the cable fitting for Ethernet cables [ W_29]. 2. Disconnect the plug from the communication circuit board. 3. Remove the interface cables from the device. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 89 TL3-S...
  • Page 90: Removing The Device

    2. Store in accordance with the technical data > [See section 4.3} Page 13] ↻ Device packaged. F Store the device at a dry location, in accordance with the ambient temperature range [See section 4.3} Page 13]. Page 90 blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S...
  • Page 91: Disposal

    Device: Do not dispose of faulty devices or accessories together with household waste. Ensure that the old devices and any accessories are disposed of in a proper manner. Packaging: Ensure that the transport packaging is disposed of properly. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 Page 91 TL3-S...
  • Page 92: Service And Warranty

    Manual Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: – Device name / serial number –...
  • Page 93: Appendix

    Unauthorised modifications to the supplied devices and/or any use of the devices that is contrary to their intended use render this Declaration of Conformity null and void. This Declaration of Conformity is issued under the sole responsibility of KACO new energy GmbH. blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137...
  • Page 94 Werner-von-Siemens-Allee 1 · 74172 Neckarsulm · Germany · Tel. +49 7132 896-0 · info@kaco-newenergy.de · www.kaco-newenergy.de...