10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Settling time
1000 – 120000
[ms] /
10
Q constant
Q constant
0 – 100 [% Slim] /
0 [% Slim] /
Underexcited | over-
excited
Output gradient in-
crease & Output gradi-
ent decrease
increasing | decreas-
ing
1 – 65,534 [% S
min] /
min] /
Settling time
1000 – 120000
[ms] /
10
Cos-phi(P)
Lock-in voltage
10 – 126.6 [% Unom] /
80 [% Unom] /
[0.1]
Lock-out voltage
10 – 126.6 [%
Unom] /
[%Unom] /
Power gradient in-
creasing & power
gradient decreasing
1 – 65,534 [% S
min] /
min] /
Settling time
1000 – 120000
[ms] /
10
Number of nodes
2 – 10
1. node ... 10. node
0V - Max. voltage in
continuous operation
Page 68
Action in this menu/meaning
Determines the dynamic behaviour in the event of a change in the cos ϕ
set value. With a reactive power change, the cos ϕ is changed according
to a PT-1 characteristic curve with a settling time of 5 Tau.
1000 [ms]
Set as a percentage of the maximum reactive power.
0.1
Reactive power mode Underexcited relates to inductive load, overex-
cited relates to capacitive load.
In addition to configuring the dynamic behaviour using the setting time
corresponding to a first-order filter, the reactive power setting can be
determined by a maximum gradient - this means the maximum change
in the reactive power per time period.
Maximum change in the reactive power %S
change to overexcited mode
/
lim
NOTE: The gradient is overlaid with the settling time.
65,534 [% S
/
lim
1
Determines the dynamic behaviour in the event of a change in the Q
target value. With a change of the reactive power or the lock-in and lock
out voltage, the Q is changed according to a PT-1 characteristic curve
1000 [ms]
with a settling time of 5 Tau.
The control is activated above this voltage.
1
The control is deactivated below this voltage.
80
0.1
Maximum change in the reactive power %S
change to overexcited mode.
NOTE: The gradient is overlaid with the settling time.
/
lim
65,534 [% S
/
lim
1
Determines the dynamic behaviour in the event of a change in the cos ϕ
set value. With a change of the active power or the lock-in and lock out
voltage, the cos ϕ is changed according to a PT-1 characteristic curve
5000 [ms]
with a settling time of 5 Tau.
Specify the number of nodes for the cos ϕ/(p/pn) characteristic curve.
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
Note: Storage inverters only for feed-in operation
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
/min in the event of a
lim
/min in the event of a
lim
TL3-S