9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
1000 – 120000
[ms] /
10
Minimum cos-phi Q1
1
2
3
4
4
- Minimum cos-phi Q4
0 – 1 /
0,001
Q(U) Active curve
1
2
4
4
3
1 - 4
Priority mode
1
2
3
4
4
Q-Priority | P-Prior-
ity
Number of nodes
1
2
3
4
4
2 - 10
Node 1- Node 10
4
1
2
3
4
Power / Excitation /
Voltage
0 – 100 [% Slim] /
43.6 [% Slim] /
Overexcited | under-
excited
0 – 125.0 [%
Unom] /
[% Unom] /
Unom]
FRT (Fault Ride
2
1
3
4
4
Through)
Page 54
Action in this menu/meaning
1. Maximum change in the reactive power in the event of a change to
overexcited mode.
2. Maximum change in the reactive power in the event of a change to
underexcited mode.
65534 [%
1
F Set the response speed of the control.
1000 [ms]
F Enter the minimum cos ϕ factor for quadrants 1 and 4.
0 /
F Select active curve.
NOTE: Up to 4 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
F Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P-priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F Specify the number of nodes.
F Set the reactive power of the node as a percentage of the maximum
power.
0.1
F Select the type of phase shift.
NOTE: Overexcited relates to a capacitive load, underexcited relates to
an inductive load.
F Enter the voltage of the node in volts.
90 ... 110.0
NOTE: The voltage values of the nodes must increase continuously. At
0.1 [%
voltages below the 1st node and voltages above the last node, the re-
active power value of the 1st or last node is used each time.
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through).NOTE:  More detailed information at: [See sec-
tion 10.3} Page 76]