8 | Commissioning

8
Commissioning
8.1

Requirements

DANGER
Lethal voltages are still present in the connections and cables of the device even after the device
has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
1. The device is only permitted to be commissioned by a qualified professional.
2. Unauthorised persons must be kept away from the device.
↻ The device has been mounted and electrically installed.
↻ The battery supplies a voltage above the configured start voltage.
1. Connect the grid voltage using the external circuit breakers.
2. Activate the battery and connect via the external DC isolator switch.
ð During initial start-up: Follow the instructions of the New Connection Wizard.
ð Following an interruption in operation Device waits for the prompt of the EMS/PMS
NOTE
A mobile terminal device with WIFI interface is required in order to put the device into operation.
The following functions are only available via the WEB interface:
1. Initial start-up
2. Setting parameters
3. Reset to factory defaults.
NOTE
We recommend using an up-to-date Firefox or Chrome browser or the default browser that is available on the
mobile terminal devices to configure the device via the web interface.
8.2

Start-up options

Option 1:
Local, guided start-up by means of WIFI
Option 2:
Local, guided start-up by means of LAN connection
Option 3:
Local start-up with pre-arranged configuration
Option 4:
Start-up in a network without Segment Controller
Page 30
– Installation technician connects to a KACO inverter via
WIFI.
– Installation wizard carries out start-up steps interact-
ively.
– Installation technician connects to a KACO inverter via
LAN.
– Installation wizard carries out start-up steps interact-
ively.
– Installation technician uses a USB memory stick that
contains a pre-prepared device configuration.
– The device imports these settings and is then ready for
operation.
– Start-up in an existing network.
– The installation technician can start up the device with
the aid of the installation wizard as described at option
1. The device can be addressed using its host name.