9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Reference power
1
2
3
4
4
Actual power |
Nominal power
Evaluated voltage
1
2
4
4
3
Maximum phase
voltage | Positive
phase sequence
voltage
Hysteresis mode
1
2
3
4
4
Off | On
Deactivation gradient
1
2
3
4
4
0 – 65534 [% / min] /
100 [% / min] /
Deactivation time
4
1
2
3
4
0 – 60000000 [ms] /
0 [ms] /
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
500 – 120000 [ms] /
2000 [ms] /
[ms]
Active curve
1
2
3
4
4
1 - 5
Number of nodes
1
2
3
4
4
2 – 5
Power
0.0 – 100.0 [% Pref] /
100 [% Pref] /
Voltage
80.0 – 125.0
[%Unom] /
0.1
Password protection
Status
Page 50
Action in this menu/meaning
F Select the power-dependent control method.
F Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
NOTE: Hysteresis mode affects the shutdown response of P(U).
F Activate the mode.
F Set the gradients for the power limitation.
1
F Specify the time for voltage reduction.
1000 [ms]
F Specify the increasing and decreasing output gradient.
65534 [%
1
F Specify the settling time.
10
F Select active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
F Specify the number of nodes.
F Specify power for 1st, 5th ... node as a percentage of the maximum
power.
1
1. Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
112 /
2. Activate optional password protection.
3. Confirm the action field.