Kaco blueplanet gridsave 92.0 TL3-S Manual page 53

Hide thumbs Also See for blueplanet gridsave 92.0 TL3-S:
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
Setting
tings
Q(P)
3
1
2
4
4
Power gradient in-
1
2
3
4
4
crease& Power gradi-
ent decrease
0 – 65535 [% Slim] /
65535 [% Slim] /
Settling time
1
2
4
4
3
200 – 60000 [ms] /
6000 [ms]
Number of nodes
1
2
3
4
4
2 - 10
Q(P) Active curve
1
2
3
4
4
1 - 10
Node 1- Node 10
1
2
3
4
4
Power Curve 1 TMP
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] /
Cos-phi Curve 1 TMP
0,3 – 1 [ind/cap] /
1 /
0.001
Overexcited | un-
derexcited
Password protection
Status
Q(U)
3
1
2
4
4
Lock-In power
1
2
3
4
4
0 – 100 [% Slim] /
100 [% Slim] /
Lock-Out power
1
2
3
4
4
0-20 [% Slim] /
[%Slim] /
Lock-In time
1
2
3
4
4
0 – 60000 [ms] /
30000 [ms] /
[ms]
Lock-Out time
0 – 60000 [ms] /
30000 [ms] /
[ms]
Dead time
1
2
3
4
4
0 -10,000 [ms] /
[ms] /
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
NOTE: Define Q(P).
F Specify the increasing and decreasing power gradient.
1
F Set the settling time in the event of an abrupt change in the rated
power target value.
1
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F Specify the number of nodes.
F Select active curve.
NOTE: Up to 10 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
F Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%, for the last node the
power must be 100%. The power values of the nodes must increase
continuously.
1
F Specify the cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Overexcited relates to a capacitive load, underexcited relates to
an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
NOTE: Define Q(U).
F Set the active power as a % of rated power above which control is ac-
tivated.
1
F Set the active power as % of rated power below which control is de-
activated.
5
1
F Set the length of time that the active power must remain above the
lock-in / lock-out power level before control is activated.
1000
1000
F Set the intentional delay for the start of the Q(U) function.
0
1
Configuration and operation | 9