10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Reference power
Actual power |
Nominal power
Evaluated voltage
1
2
3
4
4
Maximum phase
voltage | Positive
phase sequence
voltage
Hysteresis mode
Off | On
Deactivation gradient
0 – 65534 [% / min] /
100 [% / min] /
Deactivation time
0 – 60000000 [ms] /
100 [ms]
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65,534 [%/Min] /
65,534 [%/min] /
1
Settling time
1000 – 120000
[ms] /
10 [ms]
Active curve
1
2
3
4
4
1 - 5
Number of nodes
2 - 5
Power
0.0 – 100.0 [% P
100.0 [% P
Voltage
80.0 – 126.0 [%
U
] /
nom
U
] /
nom
Page 72
Action in this menu/meaning
Specifies the power reference for the characteristic curve. 100 % here
corresponds to the nominal power or the actual power at the time the
function was activated, the time when the voltage passes the con-
figured node.
F Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
Off: In non-hysteresis mode, the active power is increased immediately
with dropping voltage.
On: In hysteresis mode, the power is not increased with dropping
voltage. .
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The
limitation is implemented by an absolute power limitation that in-
1
creases with a continuous gradient up to the maximum power. The ac-
tual power of the inverter may vary freely below this limit due to a pos-
sible fluctuation in the available power or the target value, but at no
time increases above the absolute power limit.
Only evaluated with activated hysteresis mode: Monitoring time during
which the voltage must remain below the lowest configured node be-
fore the function is deactivated.
1
Specifies the dynamic response on changing the active power for power
increase. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Specifies the dynamic response on changing the active power for power
decrease. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Determines the dynamic behaviour in the event of a change in the act-
ive power set value. With a voltage change, the active power is changed
according to a PT-1 characteristic curve with a settling time of 5 Tau.
2000 [ms] /
Note: The settling time is overlaid with the increasing and decreasing
gradient.
F Select active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
up to 5 support points definable The power value of the first and last
value pair is also used as the maximum or minimum active power value
that is valid across the limits of the characteristic curve.
] /
ref
] /
0.1
ref
112.0 [%
0.1
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
TL3-S

Advertisement