4 | Technical data

4
Technical data
4.1

Electrical data

blueplanet gridsave
DC Input levels
3
Working range
3
Max. DC voltage
Starting voltage
Max. input current
Max. short-circuit current (ISC
max.)
Polarity safeguard
String fuse
DC- fuse holder
DC+ fuse holder
Number of strings
blueplanet gridsave
AC Output levels
Nominal power
Rated voltage
Voltage range: continuous op-
eration
Max. voltage range (up to 100
s)
Rated current
Max. continuous current
Contribution to peak short-cir-
cuit current ip
Initial short-circuit alternating
current (Ik" first single period
effective value)
Short circuit current continu-
ous (max output fault current)
Inrush current
Rated frequency
Frequency range
Reactive power
cos phi
Number of feed-in phases
Distortion factor (THD)
AC overvoltage protection
4.2

General data

blueplanet gridsave
General data
Display
3
For country setting UD and IL the working range can be increased to 1450 V.See table : Configuration via web
user interface [} Page 57]
Page 12
92.0 TL3-S
668-1315 V
668 V
92.0 TL3-S
92 kVA
400 V (3P+PE)
300 V - 580 V
625 V
< 3 %
Base
92.0 TL3-S
LED´s
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
110 TL3-S
Input levels (DC)
801-1315 V
1315 V
801 V
145 A
300 A
optional / with PCU yes
M yes / L yes / XL yes
no
optional
1
110 TL3-S
Output levels (AC)
110 kVA
480 V (3P+PE)
3 x 132,3 A
3 x 132,3 A
193 A
137 A
134 A
5 A [RMS (20ms)]
50/60 Hz
45 - 65 Hz
0-100 % Snom
0,3 - 1 ind/cap
3
110 TL3-S
LEDs
137 TL3-S
1002-1315 V
1002 V
137 TL3-S
137 kVA
600 V (3P+PE)
480 V - 760 V
825 V
%
Base
137 TL3-S
TL3-S

Advertisement