Kaco blueplanet gridsave 92.0 TL3-S Manual page 51

Hide thumbs Also See for blueplanet gridsave 92.0 TL3-S:
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
Setting
tings
Power Rampup
2
4
1
3
4
Power rampup gradi-
ent
Gradient
1
2
3
4
4
1 – 600 [% / min] /
10 [% / min] /
Rampup on every con-
1
2
3
4
4
nect
Rampup on first con-
nect
Rampup after grid fail-
ure
Status
Reactive Power Control
2
1
4
4
3
Mode
3
1
2
4
4
Cos-phi const. | Q
const. | Cos-phi(P/
Plim) | Q(P) | Q(U) |
Password protection
Status
Cos-phi constant
3
1
2
4
4
cos-phi const.
1
2
3
4
4
0,3 – 1 /
0,001
Power gradient in-
4
1
2
3
4
crease & Power gradi-
ent decrease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
4
1
2
3
4
1000 – 120000
[ms] /
10
Password protection
Status
Q constant
3
1
2
4
4
Q constant
4
1
2
3
4
0 – 100 [% Slim] /
0 [% Slim] /
Underexcited | over-
excited
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
NOTE: Power ramp-up is used to ramp up the power gradually. More
detailed information at: [See section 10.4.2} Page 81]
F Set increase.
1
1. Activate option.
2. Activate optional password protection.
3. Confirm action field
NOTE: Activate the reactive power process in the mode menu. More
detailed information at [See section 10.1} Page 64]
1. Select a control process.
2. Activate optional password protection.
3. Confirm the action field.
NOTE: Define the cos ϕ constant.
F Determine the specified power factor.
1 /
1. Maximum change in the reactive power %S
change to overexcited mode.
2. Maximum change in the reactive power %S
change to underexcited mode.
65534 [%
1
1. Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump).
5000 [ms]
2. Activate optional password protection.
3. Confirm the action field.
NOTE: Define the Q constant.
F Set the idle power Q to a fixed value.
0.1
F Select the type of phase shift.
NOTE: Underexcited relates to inductive load, overexcited relates to
capacitive load.
Configuration and operation | 9
/min in the event of a
lim
/min in the event of a
lim
Page 51