7 | Installation
Installing the Ethernet surge protection
↻ It has been ensured that there is no AC/DC voltage present.
1. Clamp Ethernet overvoltage protection module on the top hat rail from top to
bottom.
2. Connect the short Ethernet cable with an Ethernet port on the communication
board. [See installation instructions in the Accessories package.
3. Insert Ethernet cable through the corresponding cable fitting and insert into
overvoltage protection module.
ð Proceed with the installation of the device.
7.7

Establishing equipotential bonding

NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second ground
connection. To this end, the threaded bolt on the underside of the device can be used.
↻ The device has been installed on the mount.
1. Strip the insulation from the equipotential bonding cable.
2. Furnish the stripped cable with an M8 ring cable lug.
3. Check that the connected cable is fitted securely.
ð The housing is included in the equipotential bonding.
7.8

Connecting the interfaces

7.8.1
Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injuries or death may result from improper use of the interface connections and failure to observe pro-
tection class III.
1. The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with protec-
tion class III.
CAUTION
Damage to the device from electrostatic discharge
Components inside the device can be damaged beyond repair by static discharge.
1. Observe the ESD protective measures.
2. Earth yourself before touching a component by touching a grounded object.
All interfaces are located on the communication circuit board (HMI board) inside the housing.
Page 26
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
I
II
1
2
Fig. 25: Inserting the Ethernet over-
voltage protection
1 Ethernet overvoltage protec-
tion module (optional)
2 Top hat rail
Fig. 26: Additional earthing point