6 | Assembly and preparation

6
Assembly and preparation
6.1

Choosing the installation location

DANGER
Risk of fatal injury due to fire or explosions
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
1. Do not mount the device in potentially explosive atmospheres or in the vicinity of highly flammable materi-
als.
CAUTION
Risk of property damage due to gases that have an abrasive effect on surfaces when they come into contact
with ambient humidity caused by weather conditions!
The device housing can be seriously damaged due to gases in combination with air humidity resulting from weather con-
ditions (e.g. ammonia, sulphur).
1. If the device is exposed to gases, it must be installed in a location that is visible.
2. Perform regular visual inspections.
3. Immediately remove any moisture from the housing.
4. Ensure adequate ventilation at the installation location.
5. Immediately remove dirt, especially on vents.
6. Failure to observe these warnings may result in damage to the device that is not covered by the warranty.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or installation conditions will be billed to the cus-
tomer.
Installation space
– As dry as possible, climate-controlled, the waste heat must be dissipated away from the device.
– Unobstructed air circulation.
– Close to the ground, accessible from the front and sides without requiring additional resources.
– In outdoor areas, KACO new energy recommends protecting the device from direct weather exposure and sunlight.
This should be carried out by means of constructional measures (e.g. wind breaks) in order to reduce thermal heating
of the components, premature derating and more extensive wear of the fans.
Installation surface
– Must have adequate load-bearing capacity
– Must be accessible for installation and maintenance
– Must be made out of heat-resistant material (up to 90 °C )
– Must be flame resistant
– Minimum clearances to be observed during installation: [See figure 12 [} Page 18]