9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
1000 – 120000
[ms] /
10
Password protection
Status
Cos-phi(P)
3
1
2
4
4
Lock-In voltage
1
2
3
4
4
10 – 126.6 [%
Unom] /
Unom] /
Lock-Out voltage
1
2
3
4
4
10 – 126.6 [%
Unom] /
Unom] /
Power gradient in-
1
2
3
4
4
crease & Power gradi-
ent decrease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
1000 – 12000 [ms] /
5000 [ms]
Number of nodes
1
2
3
4
4
2 - 10
Node 1- Node 10
1
2
3
4
4
Power Curve 1 TMP
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] /
Cos-phi Curve 1 TMP
0,3 – 1 [ind/cap] /
1 /
0.001
Overexcited | un-
derexcited
Password protection
Status
Page 52
Action in this menu/meaning
1. Maximum change in the reactive power in the event of a change to
overexcited mode.
2. Maximum change in the reactive power in the event of a change to
underexcited mode.
65534 [%
1
1. Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump).
5000 [ms]
2. Activate optional password protection.
3. Confirm the action field.
NOTE: Define the cos ϕ (P).
F Set the voltage above which control is activated.
80 [%
0.1
F Set the voltage below which control is deactivated.
80 [%
0.1
1. Maximum change in the reactive power %S
change to overexcited mode.
2. Maximum change in the reactive power %S
change to underexcited mode.
65534 [%
1
F Set the settling time in the event of an abrupt change in the reactive
power target value.
10
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F Specify the number of nodes.
F Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%, for the last node the
power must be 100%. The power values of the nodes must increase
continuously.
1
F Specify the cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Overexcited relates to a capacitive load, underexcited relates to
an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137