9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Settling time
1
2
3
4
4
200 – 60000 [ms] /
1000 [ms] /
Password protection
Status
P(f)
2
1
3
4
4
Not for IL,
Operation mode
1
2
3
4
4
IT
Off | Mode 1 |
Mode 2
Power reference at un-
1
2
3
4
4
derfrequency
Actual power |
Nominal power
Power reference at
overfrequency
Actual power |
Nominal power
Dynamic gradient
1
2
3
4
4
mode
On | Off
Maximum frequency
1
2
3
4
4
for dynamic gradient
50.22 – 70.5 [Hz] /
0.01 [Hz]
Minimum frequency
for dynamic gradient
45 – 50 [Hz] /
[Hz]
Gradient at overfre-
1
2
3
4
4
quency (feed-in)
0 – 200 (%/Hz)
(%/Hz)
Gradient at underfre-
quency (feed-in)
0 – 200 (%/Hz)
(%/Hz)
Gradient in the event
1
2
3
4
4
of overfrequency -
loading
0 – 200 (%/Hz) ;
40 (%/Hz)
Gradient in the event
of underfrequency -
loading
0 – 200 (%/Hz) ;
40 (%/Hz)
Page 48
Action in this menu/meaning
1. Specify the settling time.
2. Activate optional password protection.
10
3. Confirm the action field.
NOTE: Activate frequency-dependent power reduction in the P(f)
menu.
F Specify the operation mode.
NOTE: Mode 1 = Hysteresis active; Mode 2 = Hysteresis inactive
1. Specify control method with underfrequency.
2. Specify control method with overfrequency.
F Activate dynamic gradient.
NOTE: Gradient "Feed-in/charging with over/under frequency" is not
displayed.
F Specify dynamic gradient frequency in Hz.
0.01
1. Specify gradient for feed-in with overfrequency.
2. Specify gradient for feed-in with underfrequency.
40
40
1. Determine the gradient for loading in the event of overfrequency.
2. Determine the gradient for loading in the event of underfrequency.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
TL3-S