7 | Installation
7.3.1
Requirement for supply lines and fuse
DC-Seitig
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Cable lug dimension w width max
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
AC-side
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Fuse protection for installation provided by customer (max out-
put overcurrent protection)
Fitting for AC connection
Torque for cable fitting
Schnittstellen
Cable diameter for cable fitting
Torque for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Cable diameter for cable fitting
Torque for cable fitting
Ethernet connection type
Page 22
240mm² (AL or CU)
16 - 28 mm
Depending on the cable lug
Bore for M10 screw
M40
240mm² (AL or CU)
16 - 28 mm
Bore for M10 screw
Cable lug (use the appropriate cable lug depending on
the cable material!)
M10
max. 250A
10 Nm
8 - 17 mm
Spring-type terminal
(3x) 5 - 10 mm
RJ45
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
in accordance with local installation standards
42 mm
Solar cable
30 Nm
10 Nm
in accordance with local installation standards
Depending on the cable lug
10 Nm
42 mm
10 Nm
M40
4 (M25) 1,5 (M16) Nm
0,25 - 1,5 mm²
1,5 (M16) Nm
TL3-S