9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Zero current activation
1
2
3
4
4
undervoltage
0 – 80 [% Unom]
0.1
Zero current activation
overvoltage
110 – 141.8 [%
Unom]
Reactive current limita-
1
2
3
4
4
tion
0 – 100 [ % Imax] /
100 [ % Imax] /
Minimum support time
1
2
4
4
3
1,000 – 15,000
[ms] /
10
Overvoltage protection
2
1
3
4
4
Transient overvoltage
1
2
3
4
4
protection
114.8 – 139.0 [%
Unom] /
tion 4} Page 12] /
0.1%
Password protection
Status
External grid protection
2
1
3
4
4
disconnection
External grid protection
1
2
3
4
4
Status
DC Disconnection
1
2
3
4
4
Powador-protect
4
1
2
3
4
Powador-protect oper-
ation mode
Auto | On | Off
Page 56
Action in this menu/meaning
F Set voltage threshold for zero current mode.
If one or more phase/phase or phase/neutral conductor voltages move
below or above the configured threshold, the inverter changes to zero
current mode. The total current is regulated to virtually zero.
0.1
F Set the reactive power limitation.
1
F Set the minimum support time.
5,000 [ms]
NOTE: Shutdown carried out within a grid cycle.
1. Set the transient overvoltage protection.
2. Activate optional password protection.
3. Confirm the action field.
[See sec-
NOTE: Opportunity to detect the external grid protection devices
F Select device.
NOTE: When the function is deactivated, a connected Powador-protect
and received signal, will not trigger an interruption of the DC compon-
ent.
F Activate DC shutdown on every error. Thus, the DC supply is also dis-
connected.
NOTE: Configures the grid shutdown via a Powador protect connected
to the "INV OFF" input of the device.
↻ Auto/On: A Powador-protect is operating in the photovoltaic sys-
tem and is connected to the device at the "INV OFF" input.
F Set the operating mode for Powador-protect.
Auto: The device automatically detects a Powador-protect integrated
into the photovoltaic system.
On: The digital signal of the Powador-protect must be present at the di-
gital input of the device for the device to begin feed-in.
Off: The device does not check whether a Powador-protect is integrated
into the PV plant.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
TL3-S