Manual
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
1 – 0,3 /
0.001
Overexcited | under-
excited
Q(P) 10 nodes
Power gradient in-
creasing & power
gradient decreasing
1 – 65,534 [% S
min] /
min] /
Settling time
200 – 60000 [ms] /
6000 [ms]
Number of nodes
2 – 10
1. node ... 10. node
0V - Max. voltage in
continuous operation
1 – 0,3 /
0.001
Overexcited | under-
excited
Q(U) 10 nodes
Lock-in power
0 – 100 [% S
20 [% S
lim
Lock-out power
0 – 100 [% S
[% S
] /
n
Lock-In time
0 – 60000 [ms] /
30000 [ms] /
[ms]
Lock-Out time
0 – 60000 [ms] /
30000 [ms] /
[ms]
Downtime
1
2
3
4
4
0-10000 [ms] /
[ms] /
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
1 /
Reactive power of the node as a percentage of the maximum power.
Reactive power mode Underexcited relates to inductive load, overex-
cited relates to capacitive load.
The rate of change of the output when the output power is increased is
limited by the configured value.
The rate of change of the output when the output power is decreased is
/
limited to the configured value.
lim
65,534 [% S
/
NOTE: The gradient is overlaid with the settling time.
lim
1
Sets the dynamic behaviour in the event of a change in the Q target
value. With a change in the active power, the Q target value is changed
according to a PT-1 characteristic curve with a settling time of 5 Tau.
1
Specify the number of nodes for the Q(P) characteristic curve.
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
Note: Storage inverters only for feed-in operation
1 /
Reactive power of the node as a percentage of the maximum power.
Reactive power mode Underexcited relates to inductive load, overex-
cited relates to capacitive load.
Power threshold, function is activated if limit value is exceeded.
] /
lim
] /
1
Power threshold, function is activated if limit value is undershot.
] /
5
n
1
Length of time that the active power must remain below the lock-in
power level before control is deactivated.
1000
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
1000
If the voltage switches from a characteristic curve section with Q=0 to a
characteristic curve section with Q≠0 under active control, then the re-
0
active power setting process is delayed by the set dead time. Once the
1
dead time has expired, the control circuit is no longer subject to a delay
and the set setting time determines the transient behaviour.
Specifications | 10