9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
1000 – 12000 [ms] /
5000 [ms] /
Control Mode Reactive
1
2
3
4
4
Power
Off / 0 / 1 /
Reactive power activ-
ated
0 / 1
EMS communication
1
2
3
4
4
timeout
Operation mode
1
2
4
4
3
ON | OFF
Time
4
1
2
3
4
1 – 600 [s]
Service / maintenance
1
2
3
4
4
Firmware update
2
1
3
4
4
Instant Update
3
1
2
4
4
Export Service Package
3
1
2
4
4
Service
2
1
4
4
3
Service Log
3
1
2
4
4
Logging Management
1
2
4
4
3
Settings
1
2
3
4
4
User logging interval
4
4
1
2
3
1 | 5 | 10 | 15
[minutes] /
Page 60
Action in this menu/meaning
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
65534 [%
1
F Set the settling time in the event of an abrupt change in the reactive
power target value.
10
F Select reactive power specification.
- 0 = No reactive power
- 1 = Set reactive power to a fixed value
Off
F All set values are transferred and used with 1.
NOTE: The menu item is only available in the EMS in the battery.
F Switch on the function for monitoring the system.
F Define time of interruption until signal must appear at least.
30 s
NOTE: Opportunity to perform updates, retrieve service/parameter
data and grant remote access.
NOTE: Opportunity to update the device. Parameter data are not over-
written when the firmware is updated.
1. Select and confirm the firmware update file with the "Browse..."
button
2. Load the firmware with the "Browse" button.
3. Note: During the entire update process, the AC and DC supply of the
inverter must be ensured. A loss of supply may damage the device.
Continue with update?
NOTE: Opportunity to send an error log to KACO new energy.
F Press the Export button and send the file to our service staff.
NOTE: Opportunity to specify the service interval.
NOTE: Display of all logged installations. You should also add all main-
tenance activities manually via the "Service" and "Installer" interfaces.
1. Enter additional service activities (exception: "User" interface).
2. Export service logs, if necessary.
NOTE: Input screens for log and service data and default settings.
Specify the interval for data capture and base meters.
F Specify the time period between 2 log data recordings.
NOTE: Setting and time until memory is overwritten: 1 min – 5 days; 5
5
min – 4.5 years; 10 min – 9 years; 15 min – 14 years.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137