8 | Commissioning
Required components
– Notebook with Ethernet interface
– Ethernet cable (uncrossed patch cable)
Establishing a connection to the KACO device
1. The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends
establishing a connection via WiFi.
2. The device's communication circuit board has 3 Ethernet ports that can be used:
– The 2 neighboring shielded Ethernet ports are marked LAN1 and LAN2. These ports have an internal switch and, in
their factory default state, they expect to receive an IP address from a DHCP server. As such, these can only be used if
the connected PC makes a DHCP service available.
– The port marked CON700 that can be used to speak to the device using the static IP address 169.254.1.1. This option
is preferable if you have decided to go with a wired solution.
. NOTE: Please do not under any circumstances connect the Ethernet cable to the unshielded RJ45 slot marked J200
as this typically causes damage to the printed circuit board!
1. Launch the browser on the terminal device and enter the IP address of the device:
2. http://<Geräte-IP-Adresse> (if ports LAN1 or LAN2 have been used)
3. http://169.254.1.1 (if the port marked CON700 has been used)
ð The device configuration page is displayed.
8.2.3
Start-up via a USB memory stick
Application
The installation technician has saved a pre-prepared device configuration on a USB memory stick (e.g. a configuration that
he has uploaded during the guided installation of a device or one that has been given to him by a third party).
Required components
– USB memory stick with pre-prepared start-up configuration file.
Procedure
1. Connect the USB memory stick to the USB slot on the underside of the device.
ð The device checks the saved configuration and emits a flash code via the LEDs on the front of the device which al-
lows conclusions to be drawn about the validity of the configuration ( [See section 9.2} Page 36]).
2. If the configuration is valid, the parameters are transferred.
ð Once the parameters have been adopted and the device has been restarted, the device is put into operation.
8.2.4
Starting up a network
The following illustration provides an example of the structure of a KACO unit with a string collector (SC) and an external
network connection.
MODBUS TCP /
MODBUS RTU
SUNSPEC
RS485
DC
EMS
Battery inverter
DC
Ethernet Port 0
(Static IP)
Fig. 34: Start-up via an external network
Application
If the device is to be integrated into an existing network, then the configuration shown in the figure should be used. It is
immaterial whether port LAN1 or LAN2 is used.
Required components
– A notebook that is logged into the external network.
Page 32