9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Frequency
3
1
2
4
4
Trip underfrequency
1
2
3
4
4
monitoring
Status
Number of trip under-
4
1
2
3
4
frequency levels
1 – 5 /
Trip underfrequency
1
2
3
4
4
level 1
45 – 65 [Hz] /
[Hz] /
0.01
Trip underfrequency
time level 1
0 – 1000000 [ms] /
100 [ms]
Trip underfrequency
1
2
3
4
4
level 2 - 5
42.5 – 65 [Hz] /
47.5 [Hz] /
Trip underfrequency
time level 2 – 5
0 – 1000000 [ms] /
100 /
Trip overfrequency
1
2
3
4
4
monitoring
Status
Number of trip overfre-
1
2
3
4
4
quency levels
1 – 5 /
Trip overfrequency
1
2
3
4
4
level 1
45.0 – 65 [Hz] /
51.5 [Hz] /
Trip overfrequency
time level 1
0 – 10000000 [ms] /
100 /
Trip overfrequency
1
2
3
4
4
level 2 – 5
45.0 – 67.5 [Hz] /
51.5 [Hz] /
Trip overfrequency
time level 2 – 5
0 – 10000000 [ms] /
100 /
Password protection
Status
Page 42
Action in this menu/meaning
NOTE: Opportunity to monitor frequency shutdown
F Activate if necessary.
F Specify the number of support levels.
2 /
1
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactivated.
47.5
F Define range and trip-off time.
1
0.01
1
F Activate if necessary.
F Specify the number of support levels.
2 /
1
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactivated.
1. Define range and trip-off time.
0.01
2. Activate optional password protection.
3. Confirm the action field.
1
0.01
1
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
TL3-S