3.13 o: Keypad-Related Settings
No.
Name
(Hex.)
o2-23
External 24V Powerloss
Detection
(11F8)
RUN
o2-26
Alarm Display at Ext. 24V
Power
(1563)
o2-27
bCE Detection Selection
(1565)

o3: Copy Keypad Function

No.
Name
(Hex.)
o3-01
Copy Keypad Function
Selection
(0515)
o3-02
Copy Allowed Selection
(0516)
o3-04
Select Backup/Restore
Location
(0B3E)
o3-05
Select Items to Backup/
Restore
(0BDA)
o3-06
Auto Parameter Backup
Selection
(0BDE)
o3-07
Auto Parameter Backup
Interval
(0BDF)
164
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
0 : Disabled
1 : Enabled
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
1 : Enabled
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth
Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
Sets the function that saves and copies drive parameters to a different drive with the keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup (drive →
keypad)].
0 : Disabled
1 : Enabled
Sets the storage location for drive parameters when you back up and restore parameters. This
parameter is only available when using an LCD keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
Sets which parameters are backed up, restored, and referenced. This parameter is only available when
using an LCD keypad.
0 : Standard Parameters
1 : Standard + DWEZ Parameters
Sets the function that automatically backs up parameters. This parameter is only available when
using an LCD keypad.
0 : Disabled
1 : Enabled
Sets the interval at which the automatic parameter backup function saves parameters from the drive
to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Description
Description
Default
(Range)
0
(0, 1)
1
(0, 1)
3
(0 - 4)
Default
(Range)
0
(0 - 4)
0
(0, 1)
0
(0 - 3)
1
(0, 1)
1
(0, 1)
1
(0 - 3)