Asr And Inertia Tuning - YASKAWA GA500 Maintenance & Troubleshooting

Industrial ac microdrive
Table of Contents

Advertisement

Parameter
Mode
Settings
Motor Parameter Setting
T4-01 = 0
Line-to-Line Resistance
T4-01 = 1
Auto-Tuning Input Data in EZ Open Loop Vector Control Method
To do Auto-Tuning, input data for the items in
motor test report or record the information from the motor nameplate as a reference.
Table 6.11 Auto-Tuning Input Data in EZ Open Loop Vector Control Method
Input Data
Motor Type Selection
Motor Max Revolutions
Motor Rated Revolutions
Motor Rated Frequency
Motor Rated Voltage
Motor Rated Current (FLA)
PM Motor Rated Power (kW)
Number of Motor Poles

ASR and Inertia Tuning

To increase drive responsiveness and prevent hunting, use Auto-Tuning to automatically adjust the control-related
parameters.
These types of Auto-Tuning are available for the control system:
• Deceleration Rate Tuning
• KEB Tuning
Note:
If you do Control Tuning, you cannot set H1-xx = 16 [Motor 2 Selection]. Do not do Control Tuning for applications that switch between
motor 1 and motor 2.
Parameter
Mode
Settings
Deceleration Rate
T3-00 = 2
Tuning
KEB Tuning
T3-00 = 3
Deceleration Rate Tuning
Deceleration Rate Tuning automatically sets the deceleration rate to prevent an ov [Overvoltage] fault during motor
deceleration. Set C1-11 [Accel/Decel Time Switchover Freq] first to automatically set parameters C1-02
[Deceleration Time 1] (high speed range) and C1-08 [Deceleration Time 4] (low speed range).
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Table 6.10 EZ Tuning Mode Selection
Application Conditions and Benefits
• Applicable when driving an induction motor or a PM motor
• Suitable for derating torque applications, for example fans and
pumps.
• After Auto-Tuning, the wiring distance between the drive and
motor changed by 50 m or more.
• When the motor output and drive capacity are different.
Table 6.11
Parameter
T4-02
T4-03
T4-04
T4-05
T4-06
T4-07
T4-08
T4-09
Table 6.12 Control Loop Tuning Selection
Application Conditions and Benefits
To automatically adjust the deceleration rate to prevent
an ov [Overvoltage] fault.
• To automatically adjust parameter settings to
prevent an ov [Overvoltage] fault with the KEB
Ride-Thru function.
• When L3-11 = 1 [Overvoltage Suppression Select =
Enabled].
that have an "x". Before you start Auto-Tuning, prepare the
Unit
Motor Parameter
-
-1
min
-1
min
Hz
V
A
kW
-
Applicable Control Methods (A1-02 Settings)
V/f
OLV
(0)
(2)
x
x
x
x
6.5 Auto-Tuning
Applicable Control Method
(A1-02 Setting)
EZOLV
(8)
EZOLV
(8)
Auto-Tuning Mode
(T4-01 Setting)
Setting
Line-to-Line Resistance
(0)
(1)
x
-
x
-
x
-
x
-
x
-
x
x
x
x
x
-
OLV/PM
AOLV/PM
EZOLV
(5)
(6)
(8)
x
x
x
x
x
x
6
259