YASKAWA GA500 Maintenance & Troubleshooting page 72

Industrial ac microdrive
Table of Contents

Advertisement

2.6 Parameter Setting Errors
Code
Name
oPE07
Analog Input Selection Error
Code
Name
oPE08
Parameter Selection Error
72
Causes
The settings for H3-02 and H3-10 [MFAI Function
Select] and H7-30 [Virtual Analog Input Selection]
overlap.
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = B [PID Feedback]
• H6-01 = 1 [Terminal RP Pulse Train Function =
PID Feedback Value]
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = C [PID Setpoint]
• H6-01 = 2 [PID Setpoint Value]
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = C
• b5-18 = 1 [PID Setpoint Selection = Enabled]
These parameters are set at the same time:
• H6-01 = 2
• b5-18 = 1
Causes
A function was set that is not compatible with the
control method selected in A1-02 [Control Method
Selection].
When A1-02 = 2 [OLV], you used these parameter
settings:
• n2-02 > n2-03 [Automatic Freq Regulator Time 1
> Automatic Freq Regulator Time 2]
• C4-02 > C4-06 [Torque Compensation Delay
Time > Motor 2 Torque Comp Delay Time]
When A1-02 = 0 [V/f], you used these parameter
settings:
• H6-01 = 3 [Terminal RP Pulse Train Function =
Speed Feedback (V/F Control)]
• H1-xx = 16 [MFDI Function Select = Motor 2
Selection]
When A1-02 = 5 [OLV/PM], you set E5-02 to E5-07
[PM Motor Parameters] = 0.
When A1-02 = 5, 6 [OLV/PM, AOLV/PM], you used
these parameter settings:
• E5-09 = 0.0 [PM Back-EMF Vpeak (mV/(rad/s))
= 0.0 mV/(rad/s)]
• E5-24 = 0.0 [PM Back-EMF L-L Vrms (mV/rpm)
= 0.0 mV/min
-1
]
When A1-02 = 5, 6, you set E5-09 ≠ 0 and E5-24 ≠ 0.
When A1-02 = 6, you set these parameters:
• n8-57 = 0 [HFI Overlap Selection = Disabled]
• You set E1-09 [Minimum Output Frequency] < the
5% value of E1-06.
When A1-02 = 6, you set these parameters:
• n8-35 = 0 [Initial Pole Detection Method = Pull-
in]
• n8-57 = 1 [Enabled]
When A1-02 = 8 [EZOLV], you used these parameter
settings:
• E9-01 = 1, 2 [Motor Type Selection = Permanent
Magnet (PM), Synchronous Reluctance (SynRM)]
• b3-24 = 2 [Speed Search Method Selection =
Current Detection 2]
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Possible Solutions
Set H3-02, H3-10, and H7-30 correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
• Setting value 0 [Frequency Reference]
• Setting values F and 1F [Not Used]
Remove the function settings that are not in use.
Possible Solutions
1.
Push ENTER Key to show U1-18 [oPE Fault Parameter], and
find parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx
errors have priority over oPE02.
• Set n2-02 < n2-03.
• Set C4-02 < C4-06.
Correct the parameter settings.
Note:
You cannot use Speed Feedback (V/F Control) with the Motor
Switch function.
• Set E5-01 [PM Motor Code Selection] correctly as specified by
the motor.
• For specialized motors, refer to the motor test report and set E5-
xx correctly.
Set E5-09 or E5-24 to the correct value.
Set E5-09 = 0 or E5-24 = 0.
Correct the parameter settings.
Correct the parameter settings.
When E9-01 = 1 or 2, set b3-24 = 1 [Speed Estimation].