YASKAWA GA500 Maintenance & Troubleshooting page 232

Industrial ac microdrive
Table of Contents

Advertisement

5.4 Control Circuit Wiring
Type
Terminal
MFDI
Safe Disable Input
Master Frequency
Reference
Output Terminals
Refer to
Table 5.3
and
Table 5.4
232
Table 5.2 Multi-function Input Terminals
Name (Default)
MFDI selection 1
S1
(ON: Forward run, OFF: Stop)
MFDI selection 2
S2
(ON: Reverse run OFF: Stop)
MFDI selection 3
S3
(External fault (N.O.))
MFDI selection 4
S4
(Fault reset)
MFDI selection 5
S5
(Multi-step speed reference 1)
MFDI selection 6
S6
(Multi-step speed reference 2)
MFDI selection 7
S7
(Jog command)
SN
MFDI power supply 0 V
SC
MFDI selection common
SP
MFDI power supply +24 Vdc
H1
Safe Disable input 1
H2
Safe Disable input 2
HC
Safe Disable function common
Master frequency reference pulse train input
RP
(Master frequency reference)
+V
Power supply for frequency setting
MFAI1
A1
(Master frequency reference)
MFAI2
A2
(Combined to terminal A1)
AC
Frequency reference common
for a list of Output terminals and functions.
• Photocoupler
• 24 V, 6 mA
Note:
To set the MFDI power supply (Sinking/Sourcing Mode or internal/
external power supply), install or remove a jumper between
terminals SC-SP or SC-SN depending on the application.
• Sinking Mode, Internal power supply: Install the jumper to close
the circuit between terminals SC-SP.
NOTICE: Damage to Equipment. Do not close
the circuit between terminals SC-SN. If you
close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause
damage to the drive.
• Sourcing Mode, Internal power supply: Install the jumper to close
the circuit between terminals SC-SN.
NOTICE: Damage to Equipment. Do not close
the circuit between terminals SC-SP. If you
close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause
damage to the drive.
• External power supply: Remove the jumper from the MFDI
terminals. It is not necessary to close the circuit between terminals
SC-SP and terminals SC-SN.
MFDI power supply, 24 V (maximum 150 mA)
NOTICE: Damage to Equipment. Do not close the
circuit between terminals SP-SN. If you close the
circuits between terminals SC-SP and terminals
SC-SN at the same time, it will cause damage to
the drive.
Remove the jumper between terminals H1-HC and H2-HC to use the
Safe Disable input.
• 24 V, 6 mA
• ON: Normal operation
• OFF: Coasting motor
• Internal impedance 4.7 kΩ
• OFF Minimum OFF time of 3 ms.
Safe Disable function common
NOTICE: Do not close the circuit between
terminals HC and SN. A closed circuit between
these terminals will cause damage to the drive.
• Response frequency: 0 to 32 kHz
• H level duty: 30% to 70%
• H level voltage: 3.5 V to 13.2 V
• L level voltage: 0.0 V to 0.8 V
• Input impedance: 3 kΩ
10.5 V (allowable current 20 mA maximum)
Voltage input
Use H3-01 [Terminal A1 Signal Level Select] to select the signal level.
• 0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
• -10 V to +10 V/-100% to +100% (input impedance: minimum 15
kΩ)
Voltage input or current input
Use DIP switch S1 and H3-09 [Terminal A2 Signal Level Select] to
select the input.
• 0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
• -10 V to +10 V/-100% to +100% (input impedance: minimum 15
kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250
Ω)
0 V
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING