U4: Maintenance Monitors - YASKAWA GA500 Maintenance & Troubleshooting

Industrial ac microdrive
Table of Contents

Advertisement

No.
Name
(Hex.)
U3-19
ElapsedTime@9thFault
(0812)
U3-20
ElapsedTime@10 Fault
(0813)

U4: Maintenance Monitors

No.
Name
(Hex.)
U4-01
Cumulative Ope Time
(004C)
U4-02
Num of Run Commands
(0075)
U4-03
Cooling Fan Ope Time
(0067)
U4-04
Cool Fan Maintenance
(007E)
U4-05
CapacitorMaintenance
(007C)
U4-06
PreChargeRelayMainte
(07D6)
U4-07
IGBT Maintenance
(07D7)
U4-08
Heatsink Temperature
(0068)
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Shows the cumulative operation time when the ninth most recent fault occurred.
Unit: 1 h
Shows the cumulative operation time when the tenth most recent fault occurred.
Unit: 1 h
Shows the cumulative operation time of the drive.
Use parameter o4-01 [Elapsed Operating Time Setting] to reset this monitor. Use parameter o4-02
[Elapsed Operating Time Selection] to select the cumulative operation times from:
• The time from when the drive is energized until it is de-energized.
• The time at which the Run command is turned ON.
The maximum value that the monitor will show is 99999. After this value is more than 99999, the
drive automatically resets it and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
Shows how many times that the drive has received a Run command.
Use parameter o4-13 [RUN Command Counter @ Initialize] to reset this monitor. The maximum
value that the monitor will show is 65535. After this value is more than 65535, the drive
automatically resets it and starts to count from 0 again.
Unit: 1
Shows the cumulative operation time of the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor. The maximum value that
the monitor will show is 99999. After this value is more than 99999, the drive automatically resets it
and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
Shows the cumulative operation time of the cooling fans as a percentage of the estimated
performance life of the cooling fans.
The default value is 0. The value counts up from 0.
Use o4-03 [Fan Operation Time Setting] to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is at 90%.
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the estimated performance life of the electrolytic capacitors.
The default value is 0. The value counts up from 0.
Use o4-05 [Capacitor Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is at 90%.
Shows the operation time of the soft charge bypass relay as a percentage of the estimated
performance life of the soft charge bypass relay.
The default value is 0. The value counts up from 0.
Use o4-07 [Softcharge Relay Maintenance Set] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is at 90%.
Shows the operation time of the IGBTs as a percentage of the estimated performance life of the
IGBTs.
The default value is 0. The value counts up from 0.
Use o4-09 [IGBT Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is at 90%.
Shows the heatsink temperature of the drive.
Unit: 1 °C
Description
Description
3.17 U: Monitors
MFAO Signal Level
No signal output available
No signal output available
MFAO Signal Level
10 V: 99999 h
10 V: 65535 times
10 V: 99999 h
10 V: 100%
10 V: 100%
10 V: 100%
3
10 V: 100%
10 V: 100 °C
177