Item
1000 m (3281 ft) Maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
Altitude
It is not necessary to derate the rated voltage in these conditions:
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the neutral point on the power supply.
Contact Yaskawa or your nearest sales representative if you will not ground the neutral point.
• 10 Hz to 20 Hz: 1 G (9.8 m/s
Vibration
• 20 Hz to 55 Hz: 0.6 G (5.9 m/s
Installation
Install the drive vertically for sufficient airflow to cool the drive.
Orientation
Item
• UL 61800-5-1
• EN 61800-3
Applicable Standards
• EN 61800-5-1
• Two Safe Disable inputs and one EDM output according to EN ISO 13849-1 (Cat.3, PL e), EN 61800-5-2 SIL3
IP20/UL Open Type
IP20/UL Type 1
Enclosure Protection
Design
Note:
Install a UL Type 1 kit (optional) on an IP20/UL Open Type drive to change the drive to an IP20/UL Type 1 enclosure.
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Specification
2
, 32.15 ft/s
2
)
2
, 19.36 ft/s
2
)
Table 7.11 Standard
Specification
7.5 Drive Specifications
273