Maximum Applicable Motor Output (kW)
Maximum Applicable Motor Output (HP)
Input
Rated Input Current (A)
Rated Output Capacity (kVA)
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage
Maximum Output Frequency
Measures for
DC Link Choke
Harmonics
Braking Device
Braking Transistor
EMC Filter
EMC Filter
IEC61800-3
Rated Voltage/Rated Frequency
Permitted Voltage Fluctuation
Power Supply
Permitted Frequency Fluctuation
Input Power (kVA)
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 220 V.
Model
Maximum Applicable Motor Output (kW)
Maximum Applicable Motor Output (HP)
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Table 7.4 Ratings (Three-Phase 200 V Class)
Model
*1
HD
*2
ND
*1
HD
*2
ND
HD (AC)
HD (DC)
ND (AC)
ND (DC)
HD
*3
ND
HD
ND
HD
ND
Table 7.5 Ratings (Three-Phase 200 V Class)
*1
HD
*2
ND
*1
HD
*2
ND
7.3 Model Specifications (Three-Phase 200 V Class)
2010
2012
1.5
2.2
2.2
3
2
3
3
4
7.5
11
9.2
13.5
10.8
13.9
13.2
17
3
4.2
3.7
4.6
8.0
11.0
9.6
12.2
• HD: 150% of the rated output current for 60 seconds. The permitted frequency of
overload is one time each 10 minutes.
• ND: 110% of the rated output current for 60 seconds. The permitted frequency of
overload is one time each 10 minutes.
Note:
Derating can be necessary for applications that start and stop frequently.
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
• V/f, OLV, OLV/PM: 590 Hz
• AOLV/PM: 270 Hz
• EZOLV: 120 Hz
External options
Standard internal characteristics
Factory option
Models 2xxxE: Category C3 (Conducted emission)
• Three-phase AC power supply 200 V to 240 V at 50/60 Hz
• DC power supply 270 V to 340 V
-15% to +10%
±5%
3.4
5.0
4.9
6.4
2042
2056
7.5
11
11
15
10
15
10
20
2021
2030
3.7
5.5
5.5
7.5
5
7.5
7.5
10
18.9
24
23.1
29.4
24
37
29.4
45.3
6.7
9.5
8
11.4
17.6
25.0
21
30
8.7
11.0
11
17.0
2070
2082
15
18.5
18.5
22
20
25
25
30
267