YASKAWA GA500 Maintenance & Troubleshooting page 74

Industrial ac microdrive
Table of Contents

Advertisement

2.6 Parameter Setting Errors
Code
Name
oPE33
Digital Output Selection Error
74
Causes
These two parameters are set at the same time:
• H2-60 ≠ F [Term MA,MB,MC Secondary Function
≠ Not Used]
• H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ F [Terminal P1 Secondary Function ≠
Not Used]
• H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ F [Terminal P2 Secondary Function ≠
Not Used]
• H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
These parameter pairs are set incorrectly:
• H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
• H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
If you use the function to output logical calculation results (H2-
60, H2-63, H2-66 ≠ F), you cannot set H2-01 to H2-03 = 1xx.
• Set parameters H2-21 ≤ H2-22.
• Set parameters H2-27 ≤ H2-28.