2.6 Parameter Setting Errors
Code
Name
oPE33
Digital Output Selection Error
74
Causes
These two parameters are set at the same time:
• H2-60 ≠ F [Term MA,MB,MC Secondary Function
≠ Not Used]
• H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ F [Terminal P1 Secondary Function ≠
Not Used]
• H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ F [Terminal P2 Secondary Function ≠
Not Used]
• H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
These parameter pairs are set incorrectly:
• H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
• H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
If you use the function to output logical calculation results (H2-
60, H2-63, H2-66 ≠ F), you cannot set H2-01 to H2-03 = 1xx.
• Set parameters H2-21 ≤ H2-22.
• Set parameters H2-27 ≤ H2-28.