6.2

Overview of Keypad Components and Functions

Symbol
Name
A
USB Terminal Pass-through
RUN Key
B
STOP Key
C
LO/RE LED
D
ALM/ERR LED
E
READY LED
F
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Figure 6.1 Keypad
Table 6.1 Keypad Components and Functions
Pass-through point to connect a USB cable to the drive to use the DriveWizard PC tool or the DriveWizard Mobile App to program
the drive. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the drive to a PC, Android smartphone, or tablet.
Starts the drive in LOCAL Mode.
Starts the operation in Auto-Tuning Mode.
Note:
Before you use the keypad to operate the motor, push
Stops drive operation.
Note:
Uses a stop-priority circuit. Push
active at an external Run command source. To disable
Disabled].
Illuminated: The keypad controls the Run command (LOCAL Mode).
OFF: The control circuit terminal or serial transmission device controls the Run command (REMOTE Mode).
Note:
• LOCAL: Use the keypad to operate the drive. Use the keypad to enter Run/Stop commands and the frequency reference
command.
• REMOTE: Use the control circuit terminal or serial transmission to operate the drive. Use the frequency reference source
entered in b1-01 and the Run command source selected in b1-02.
Illuminated: The drive detects a fault.
OFF: There are no drive faults or alarms.
Flashing:
• Alarm
• Operation Errors
• An Auto-Tuning error
Note:
The LED will illuminate to identify a fault if the drive detects a fault and an alarm at the same time.
Illuminated: The drive is operating or is ready for operation.
OFF:
• The drive detects a fault.
• There is no fault and the drive received a Run command, but the drive cannot run. For example, in Programming Mode.
Flashing: The drive is in STo [Safe Torque OFF] condition.
Flashing quickly: The voltage of the main circuit power supply is not in the drive nameplate specifications, and the external 24 V
power supply is providing the only power to the drive.

6.2 Overview of Keypad Components and Functions

Function
on the keypad to set the drive to LOCAL Mode.
to stop the motor. This will also apply when a Run command (REMOTE Mode) is
priority, set o2-02 = 0 [STOP Key Function Selection =
6