YASKAWA GA500 Maintenance & Troubleshooting page 103

Industrial ac microdrive
Table of Contents

Advertisement

No.
Name
(Hex.)
b5-12
Feedback Loss Detection
Select
(01B0)
b5-13
PID Feedback Loss
Detection Lvl
(01B1)
b5-14
PID Feedback Loss
Detection Time
(01B2)
b5-15
PID Sleep Function Start
Level
(01B3)
b5-16
PID Sleep Delay Time
(01B4)
b5-17
PID Accel/Decel Time
(01B5)
RUN
b5-18
b5-19 PID Setpoint Selection Sets the function that enables and disables b5-19 [PID Setpoint Value].
(01DC)
b5-19
PID Setpoint Value
(01DD)
RUN
b5-20
PID Unit Selection
(01E2)
b5-34
PID Output Lower Limit
Level
(019F)
RUN
b5-35
PID Input Limit Level
(01A0)
RUN
b5-36
PID High Feedback
Detection Lvl
(01A1)
b5-37
PID High Feedback
Detection Time
(01A2)
b5-38
PID User Unit Display
Scaling
(01FE)
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Sets the drive response to PID feedback loss/excess. Sets drive operation after the drive detects PID
feedback loss/excess.
0 : Digital Out Only, Always Detect
1 : Alarm + Digital Out, Always Det
2 : Fault + Digital Out, Always Det
3 : Digital Out Only, @ PID Enable
4 : Alarm + Digital Out, @PID Enable
5 : Fault + Digital Out, @PID Enable
Sets the level that triggers PID Feedback Loss [FbL] detection as a percentage of the Maximum
Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Sets the length of time that PID Feedback must be less than b5-13 [PID Feedback Loss Detection
Lvl] to detect PID Feedback Loss [FbL].
Sets the output level that triggers the PID Sleep function.
Sets a delay time to start or stop the PID Sleep function.
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive. This
is a soft-starter for the PID setpoint.
0 : Disabled
1 : Enabled
Sets the PID setpoint when b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled].
Sets the number of digits to set and show the PID setpoint.
0 : 0.01Hz units
1 : 0.01% units
2 : rev/min
3 : User Units
Sets the lower limit level for the PID control as a percentage of E1-04 [Maximum Output
Frequency].
When you use b5-34, set b5-91 = 0 [EZ Sleep Minimum Speed = 0 (Disabled)].
When you set the output lower limit level as Hz units or min
reference
ID.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Sets the output upper limit for the PID control as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Sets the level that triggers Excessive PID Feedback [FbH] as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Sets the length of time that the PID feedback signal must be more than the level set in b5-36 [PID
Feedback High Detection Lvl] to cause Excessive PID Feedback [FbH].
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
Description
-1
(r/min) units, refer to page
3.5 b: Application
Default
(Range)
0
(0 - 5)
0%
(0 - 100%)
1.0 s
(0.0 - 25.5 s)
Determined by A1-02
(0.0 - 590.0)
0.0 s
(0.0 - 25.5 s)
0.0 s
(0.0 - 6000.0 s)
0
(0, 1)
0.00%
(0.00 - 100.00%)
1
(0 - 3)
0.0%
(-100.0 - +100.0%)
Missing
1000.0%
(0.0 - 1000.0%)
100%
(0 - 100%)
1.0 s
(0.0 - 25.5 s)
Determined by b5-20
(1 - 60000)
103
3

Advertisement

Table of Contents
loading

Table of Contents