2.5 Minor Faults/Alarms
Code
Name
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
Code
Name
EF5
External Fault (Terminal S5)
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
Code
Name
EF6
External Fault (Terminal S6)
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
Code
Name
EF7
External Fault (Terminal S7)
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
Code
Name
EP24v
External Power 24V Supply
Note:
• Set o2-26 [Ext. Power 24V Supply Display] to enable or disable EP24v detection.
• The drive will not output an alarm signal for this alarm.
Code
Name
FbH
Excessive PID Feedback
Note:
• The drive detects this error if the PID feedback input is more than the level set in b5-36 for longer than b5-37.
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it will operate the motor as specified by the stopping method set in b5-12 [Feedback Loss Detection Select].
Code
Name
FbL
PID Feedback Loss
64
Causes
External Fault [H1-04 = 2C to 2F] is set to MFDI
terminal S4, but the terminal is not in use.
Causes
MFDI terminal S5 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-05 = 2C to 2F] is set to MFDI
terminal S5, but the terminal is not in use.
Causes
MFDI terminal S6 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-06 = 2C to 2F] is set to MFDI
terminal S6, but the terminal is not in use.
Causes
MFDI terminal S7 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-07 = 2C to 2F] is set to MFDI
terminal S7, but the terminal is not in use.
Causes
The voltage of the main circuit power supply
decreased, and the 24 V power supply is supplying
power to the drive.
Causes
The FbH detection level is set incorrectly.
There is a problem with the PID feedback wiring.
The feedback sensor is not operating correctly.
A fault occurred in the feedback input circuit of the
drive.
Causes
The FbL detection level is set incorrectly.
There is a problem with the PID feedback wiring.
The feedback sensor is not operating correctly.
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Possible Solutions
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S5.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S6.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S7.
Correctly set the MFDI.
Possible Solutions
• Examine the main circuit power supply.
• Turn ON the main circuit power supply to run the drive.
Possible Solutions
Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID
High Feedback Detection Time].
Correct errors with the PID control wiring.
Examine the sensors on the control device side.
Replace the board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales representative.
Possible Solutions
Adjust b5-13 [PID Feedback Loss Detection Lvl] and b5-14 [PID
Feedback Loss Detection Time].
Correct errors with the PID control wiring.
Examine the sensors on the control device side.