9.5

After the test is finished

After the test is finished, the CT-Object card displays the CT data determined during the test. Refer to
section 5.2.4 on page 60 for more information.
9.6

Disconnection

After the CT test is finished, disconnect the CT under test from CT Analyzer.
WARNING
Death or severe injury caused by high voltage or current possible
As long as the red LED on the CT Analyzer test set is flashing, the output is active and
lethal voltages can occur due to the high energy stored in external inductors.
► Do not disconnect measurement leads while the red LED on CT Analyzer is flashing.
► Always wait until the red LED is off before disconnecting measurement leads.
1. Wait until the red LED on CT Analyzer is off.
2. Disconnect the measurement leads starting at CT Analyzer.
OMICRON
Using the guesser function
141