CT Analyzer User Manual
Table 12-4: Measurement input PRIM
Characteristic
Voltage ranges
Accuracy
Insulation
12.4

Winding resistance measurement accuracy

Table 12-5: Winding resistance measurement accuracy
Characteristic
Resolution
Accuracy
12.5

Ratio and phase measurement accuracy

The values given in the following table are only valid under the following conditions:
All utility lines to the primary side of the CT are disconnected.
One terminal of the primary side of the CT is connected to PE.
The original measurement cables delivered by OMICRON for CT Analyzer are used.
The CT under test is a CT with a non-gapped core.
The knee point voltage according to IEEE C57.13 is > 3V.
Under interfering conditions the device has reduced accuracy.
Values without the prefix "!" in the ratio table of the Ratio card have guaranteed accuracy. The accuracy
of values marked with a "!" in the table is reduced by factor 2 since these values are not directly
measured but calculated from the measured values instead.
Table 12-6: Ratio measurement accuracy for 1 A CTs at rated current
CT ratio
0.2 - 1
> 1 - 2000
> 2000 - 5000
> 5000 - 10000
1. Nominal burden of the CT.
170
Rating
0 - 0.03 / 0.3 / 3 / 30V
AC
0.1% (guaranteed)
Reinforced insulation (R) to all other circuits
Rating
Ω
1m
0.05% (typical)
Ω
0.1% + 1m
(guaranteed)
I
Rated power
sn
1
1.0 - 30VA
1
0 - 30VA
1
0 - 30VA
1
0 - 30VA
(auto ranging)
1
Typical accuracy
0.05%
0.02%
0.03%
0.05%
Guaranteed
accuracy
0.1%
0.05%
0.1%
0.2%
OMICRON