Setup And Connection; General Safety Rules For Connecting And Operating Ct Analyzer - Omicron CT SB2 User Manual

Ct analyzer
Hide thumbs Also See for CT SB2:
Table of Contents

Advertisement

3

Setup and connection

3.1
General safety rules for connecting and operating
CT Analyzer
Observe the following general safety rules and the safety instructions given in chapter 1 "Safety
instructions" on page 9 when connecting and operating CT Analyzer. The safety rules given here are
supplemented by further notes and warnings applicable for specific actions only. Such specific notes and
warnings are given where necessary in this user manual.
► Before putting CT Analyzer into operation, check the test set for visible damages.
► When taking CT Analyzer into operation, make sure that the air slots, the power switch and the power
supply plug at the test set are not obstructed and that the test set can be easily disconnected from
mains.
► Only use wires with 4mm safety "banana" connectors and plastic housing for connection to the front
panel input/output sockets.
► During the test always connect one terminal of the transformer's primary side to protective earth.
WARNING
Death or severe injury caused by high voltage or current possible
► Make sure that the terminals of the test object to be connected to CT Analyzer do not
carry any voltage potential.
► During a test, CT Analyzer is the only permitted power source for the test object.
WARNING
Death or severe injury caused by high voltage or current possible
As long as the red LED on the CT Analyzer test set is flashing, the output is active and
lethal voltages can occur due to the high energy stored in external inductors.
► Do not touch the equipment under test or the measurement leads while the red LED
on CT Analyzer is flashing.
► Never connect or disconnect measurement leads while the red LED on CT Analyzer is
flashing.
WARNING
Death or severe injury caused by high voltage or current possible
Accidentally mixing up primary and secondary windings can cause life-threatening
voltages and/or destroy the connected CT or the CT Analyzer test set.
► Always make sure that the CT Analyzer output is connected to the correct side of the
current transformer according to the wiring instructions given in sections 3.4 to 3.5
below.
OMICRON
Setup and connection
23