204.xxx
Warning [204.xxx] Check CT SB2 switch box wiring: Wrong polarity at PRIM terminal.
Reason:
Solution:
205.xxx
Warning [205.xxx] Check connection. Input PRIM may be disconnected.
Reason:
Solution:
205.xxx
Warning [205.xxx] Check CT SB2 switch box wiring: PRIM IN terminal may be disconnected.
Reason:
Solution:
206.xxx
Warning [206.xxx] Check connection. Ensure that the output is connected to the primary side of
the CT.
Reason:
Solution:
206.xxx
Warning [206.xxx] Check CT SB2 switch box wiring: CTA OUTPUT and/or PRIM OUT terminal may
be disconnected.
Reason:
Solution:
207.xxx
Warning [207.xxx] Check connection! OUTPUT may be disconnected.
Reason:
Solution:
210.xxx
Warning [210.xxx] Permanent data overflow.
Reason:
Solution:
211.xxx
Warning [211.xxx] Sinus mode measurement timeout.
Reason:
Solution:
220.xxx
Warning [220.xxx] Test aborted!
Reason:
Solution:
308.xxx
Note [308.xxx] I-sn value has to be specified in CT-Object Card prior to Residual Magnetism test!
Reason:
Solution:
310.xxx
Note [310.xxx] License: <Guesser functionality> is missing! Values for: Ipn, Isn, P/M, Class,
FS/ALF should be provided.
Reason:
Solution:
311.xxx
Warning [311.xxx] License: <Simulation after test> is missing!
Reason:
Solution:
312.xxx
Warning [312.xxx] License: <...> is missing!
Reason:
Solution:
OMICRON
Input signal at input "PRIM" differs from the expected one: Reverse polarity at CT SB2
input "PRIM".
Check whether the PRIM IN sockets on the CT SB2 are connected properly and with
correct polarity. If necessary, connect with changed polarity.
Input signal at input "Prim" differs from the expected one.
Check whether the output generator ("Output") and measurement input "Prim" are
connected properly.
Input signal at input "Prim" differs from the expected one.
Check whether the PRIM IN sockets on the CT SB2 are connected properly.
Input signal at input "Prim" differs from the expected one.
Check that the output generator ("Output") is connected to the CT and that the primary side
of the CT is connected to input "Prim".
Input signal at input "Prim" differs from the expected one.
Check whether the PRIM OUT and the PRIM IN sockets on the CT SB2 are connected
correctly to the primary side of the CT.
The current signal differs from the expected one.
Check whether the output generator ("Output") and measurement input "SEC" are
connected properly to the secondary side of the CT.
Internal data buffer overflow. The data could not be fetched fast enough from the internal
data buffer.
Try to repeat the measurement. If this error occurs more frequently, you should contact
your next OMICRON service center.
Measurement timeout due to frequent range switching or invalid data from the
measurement inputs.
Check the wiring and repeat the measurement. Try to reduce noise for the measurement.
The test sequence has been interrupted by the user.
Repeat the test without interrupting it.
For the remanence test the I
Enter valid I
value before starting the remanence test.
sn
The license required for class guessing is not available.
Specify the values for I
pn
The license required for simulation is not available.
Simulation of the results for changed test settings (e.g. different burden values) after the
test is not possible. Purchase a corresponding license.
The license specified in the message is not available.
The functionality included in the license is not available. Purchase a corresponding license.
value should be defined.
sn
, I
, Class, P/M and FS/ALF before starting the test.
sn