Omicron CT SB2 User Manual page 102

Ct analyzer
Hide thumbs Also See for CT SB2:
Table of Contents

Advertisement

CT Analyzer User Manual
Specific parameters and settings displayed for IEC 61869-2 protection CTs
The following parameters are only displayed in the CT-Object card if the standard IEC 61869-2 is
selected with the type "Protection CT".
Table 8-8: Parameters and settings for IEC 61869-2 protection CTs
Param.
Description
ALF
Accuracy limiting factor acc. to IEC 61869-2.
Possible values: Integer value from 1 to 300 or soft
1
keys ?
, 5, 10, 15, 20 or 30.
Default: ?.
Rct
Specified secondary winding resistance.
Possible values: 0 to 3000 ohms or soft key ?
Default: ?
Ts
Specified secondary time constant.
Possible values: 0.000 to 100.0s or soft key ?
Default: 100s.
Kx
Dimensioning factor acc. to IEC 61869-2.
Possible values: 1 to 300 or soft key ?
Default: ?.
Ek
Rated knee point e.m.f.
Possible values: 0 to 40000V or soft key ?
Default: ?.
E1
User-defined e.m.f. to verify the excitation current
at this specific e.m.f.
Possible values: 0.1 to 40000V or soft key ?
Default: ?.
Ie
Accuracy limiting current acc. to IEC 61869-2.
Possible values: 0.03mA to 30000mA or
1
soft key ?
Default: ?.
Ie1
Maximum allowed excitation current at E
Possible values: 0.03mA to 30000mA or soft key
3
?
.
Default: ?.
100
.
Available for IEC 61869-2 protection
CTs, class
protection
...P
...PR PX
x
x
1
x
.
1
x
.
1
.
1
.
2
.
.
1
transient
protection
PXR TPX TPY TPZ
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x