System Under Test - Omicron DANEO 400 User Manual

Table of Contents

Advertisement

DANEO 400
5.1.3

System under test

In System Under Test, you create the substation system. Therefore, load an SCL file including the
GOOSE and Sampled Values or manually add an IED. Only selected IEDs are used for testing.
The GOOSE and Sampled Values of the loaded substation system can be verified against the
network. For further details, refer to section "IEC 61850 SCL verification" on page 35.
Loading SCL files
Loading an SCL file imports the GOOSE and Sampled Values configurations of IEDs.
To load an SCL file, in the System Under Test section, click Load SCL file.
Note: The following SCL file extensions are supported: .scd, .icd, .cid, .iid, .sed, .xml.
The following table shows possible issues while loading an SCL file.
Issues while loading an SCL file
The SCL file contains IEDs already
included in the system under test, but
with different settings.
The SCL file contains the same IED
twice.
Manually adding, selecting, and removing IEDs
To manually add an IED:
1. On the Navigation pane, click IEDs.
2. In the System Under Test section, click Add. The newly created IED appears in the
Loaded IEDs table.
To select IEDs for testing, select the Used check box either in the System Under Test section or in
the Navigation pane. The selected IEDs are included in a subset that is used for all subsequent tasks
concerning IEDs.
When you clear an IED check box, the IED is no longer used for testing, but its GOOSE and Sampled
Values remain persisted.
To remove IEDs, in the System Under Test section, select the IEDs, and then click Remove. You can
use Ctrl and Shift for multiple selections.
When you remove an IED, its GOOSE and Sampled Values are deleted and removed from all views.
34
Choose whether to replace the existing IEDs by the
imported IEDs.
Only the first IED is parsed and loaded.
Result