7.3.3
Secondary winding resistance measurement details
Press the Wdg. Res. Test soft key in the Test Results card to display the secondary winding resistance
measurement details.
Figure 7-5: Winding resistance measurement details
Table 7-7: Test results for secondary winding resistance measurement
Parameter
Description
I-DC
Current used for measurement. Selected automatically, cannot be changed by the
user.
If I
sn
If I
sn
Maximum value: 5 A.
V-DC
Measured voltage.
R-meas
Measured resistance at ambient temperature.
R-ref
Reference resistance (temperature-compensated resistance, compensated to T
T-meas
Winding temperature of the CT at the time of measurement.
Value used:
Ambient Temperature defined in the Settings (main menu).
If this temperature is not set correctly, the reference resistance value (R
reference temperature will not be calculated correctly.
T-ref
Reference temperature, i.e, temperature the CT is specified for.
Value used:
Reference temperature defined in the Settings (main menu).
The winding resistance at reference temperature is calculated from the winding
resistance measured at ambient temperature (T
temperature.
OMICRON
is 0.2 A or higher, I
is automatically set to I
DC
is lower than 0.2 A, I
DC
sn
is automatically set to 0.2 A.
meas
Test cards for CT Test mode
.
) at
ref
) and the specified reference
).
ref