ABB ACS880 Firmware Manual page 55

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
110.13
DI5 ON delay
Connected
signal
status
DI status
0.0 ... 3000.0 s
110.14
DI5 OFF delay
0.0 ... 3000.0 s
110.15
DI6 ON delay
Connected
signal
status
DI status
0.0 ... 3000.0 s
110.16
DI6 OFF delay
0.0 ... 3000.0 s
110.21
RO status
0000h...FFFFh
110.24
RO1 source
Not energized
Energized
Ready
Started
Ready run
Description
Defines the activation delay for digital input DI5.
t
t
On
Off
t
110.13 DI5 ON delay
On
t
110.14 DI4 OFF delay
Off
Activation delay for DI5.
Defines the deactivation delay for digital input DI5. See
parameter
110.13 DI5 ON
Deactivation delay for DI5.
Defines the activation delay for digital input DI6.
t
t
On
Off
t
110.15 DI6 ON delay
On
t
110.16 DI6 OFF delay
Off
Activation delay for DI6.
Defines the deactivation delay for digital input DI6. See
parameter
110.15 DI6 ON
Deactivation delay for DI6.
Shows the status of relay outputs RO8...RO1.
Example: 00000001 = RO1 is energized, RO2...RO8 are
de-energized.
Status of relay outputs.
Selects a signal to be connected to relay output RO1.
Note: For the cabinet-installed supply units, check the
delivery-specific use from the delivery-specific circuit
diagrams. Do not change the setting if relay output is in
use and connected already.
Relay output is not energized.
Relay output is energized.
Bit 0 of
106.11 Main status word
energized when the supply unit is ready.
Bit 4 of
106.16 Drive status word 1
energized when the supply unit is started.
Bit 1 of
106.11 Main status word
energized when the supply unit is ready.
1
0
1
0
Time
t
t
On
Off
delay.
1
0
1
0
Time
t
t
On
Off
delay.
(see page 47). Relay is
(see page 47). Relay is
(see page 47). Relay is
Parameters 55
Def/FbEq16
0.0 s
10 = 1 s
0.0 s
10 = 1 s
0.0 s
10 = 1 s
0.0 s
10 = 1 s
1 = 1
Running
0
1
2
3
4