ABB ACS880 Firmware Manual page 92

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

92 Parameters
No.
Name/Value
120.04
Ext1 in2
120.06
Ext2 commands
Not sel
In1 Start
In1P Start; In2 Stop The sources of the start and stop commands are
Keypad
Fieldbus A
DDCS controller
120.07
Ext2 start trigger
Edge
Level
120.08
Ext2 in1
120.09
Ext2 in2
120.12
Run enable 1
Description
Selects source 2 for external control location EXT1. See
parameter
120.01 Ext1
For the available selections, see parameter
in1.
Selects the source of start and stop commands for
external control location 2 (EXT2).
Note: This parameter cannot be changed while the
converter is running.
No start or stop command sources selected.
The source of the start and stop commands is selected
by parameter
120.08 Ext2
the source bit are interpreted as follows:
State of source
(120.08)
0 - > 1
1 - > 0
selected by parameters
in2. The state transitions of the source bits are
interpreted as follows:
State of source 1
State of source 2
(120.08)
0 - > 1
Any
Any
The start and stop commands are taken from the
control panel (or PC connected to the control panel).
The start and stop commands are taken from fieldbus
adapter A.
The start and stop commands are taken from an
external (DDCS) controller.
Defines whether the start signal for external control
location EXT2 is edge-triggered or level-triggered.
Note: In case the settings of parameters
120.07
are in conflict, the setting of parameter
takes preference.
The start signal is edge-triggered.
The start signal is level-triggered.
Selects source 1 for external control location EXT2. See
parameter
120.06 Ext2
For the available selections, see parameter
in1.
Selects source 2 for external control location EXT2. See
parameter
120.06 Ext2
For the available selections, see parameter
in1.
Selects the source of the external run enable signal. If
the run enable signal is switched off, the supply unit will
not start, or stops if running.
1 = Run enable.
Note: This parameter cannot be changed while the
converter is running.
commands.
120.03 Ext1
in1. The state transitions of
Command
Start
Stop
120.08 Ext2 in1
and
120.09 Ext2
Command
(120.09)
1
1 - > 0
0
120.06
commands.
120.03 Ext1
commands.
120.03 Ext1
Def/FbEq16
DI2
Not sel
0
1
4
Start
Stop
Stop
11
12
16
Edge
and
120.06
0
1
Off
Off
DI2