ABB ACS880 Firmware Manual page 104

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

104 Parameters
No.
Name/Value
Cabinet fan
DC-capacitor
133.20
On-time 2 act
0 ... 4294967295 s
133.21
On-time 2 limit
0 ... 4294967295 s
133.22
On-time 2 func
Bit
0
1
2...15
0000h...FFFFh
133.23
On-time 2 src
False
True
RO1
Other [bit]
133.24
On-time 2 warn sel
On-time 2
Device clean
Add cool fan
Cabinet fan
DC-capacitor
133.30
Edge count 1 act
0...4294967295
133.31
Edge count 1 limit
0...4294967295
Description
AE4D Cabinet fan
AE4C DC capacitor
Reading of on-time timer 2. Can be reset from the Drive
composer PC tool, or from the control panel by keeping
Reset depressed for over 3 seconds.
Reading of on-time timer 2.
Sets the warning limit for on-time timer 2.
Warning limit for on-time counter 2.
Configures on-time timer 2. This timer runs whenever
the signal selected by parameter
on.
After the limit set by
the warning specified by
given (if enabled by this parameter), and the timer reset.
The current value of the timer is readable from
parameter
133.20 On-time 2
status
indicates that the time has exceeded the limit.
Function
Counter mode
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds
1 = Saturate: If warning is enabled by bit 1, it stays active until reset
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning is given when the limit is reached
Reserved
On-time timer 2 configuration word.
Selects the signal to be monitored by on-time timer 2.
Constant 0.
Constant 1.
Bit 0 of
110.21 RO status
Source selection (see
39).
Selects the warning message for on-time timer 2.
AE46 On-time
AE4B Device clean
AE4F Additional cooling fan
AE4D Cabinet fan
AE4C DC capacitor
Reading of signal edge counter 1. Can be reset from the
Drive composer PC tool, or from the control panel by
keeping Reset depressed for over 3 seconds.
Reading of signal edge counter 1.
Sets the warning limit for signal edge counter 1.
Warning limit for signal edge counter 1.
warning.
warning.
133.23 On-time 2 src
133.21 On-time 2 limit
133.24 On-time 2 warn sel
act. Bit 1 of
(page 55).
Terms and abbreviations
2.
warning.
warning.
warning.
warning.
Def/FbEq16
8
9
-
1 = 1 s
0 s
1 = 1 s
00b
is
is reached,
is
133.01 Counter
1 = 1
False
0
1
2
on page
-
On-time 2
1
6
7
8
9
-
1 = 1
0
1 = 1

Advertisement

Table of Contents
loading

Table of Contents