ABB ACS880 Firmware Manual page 99

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
131.15
Total trials time
1.0 ... 600.0 s
131.16
Delay time
0.0 ... 120.0 s
131.28
Ext earth leakage
signal source
Active (false)
Inactive (true)
DIIL
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
131.29
Ext earth leakage
action
Warning
Fault
131.32
Aux circuit breaker
fault source
Active (false)
Inactive (true)
DIIL
Description
Defines the time for the automatic reset function. See
parameter
131.14 Number of
Time for automatic resets.
Defines the time that the supply unit will wait after a
fault before attempting an automatic reset. See
parameter
131.12 Autoreset
Autoreset delay.
Defines the source of earth leakage fault indication.
Signal value is decoded as follows:
0 = Earth leakage fault
1 = No earth leakage fault.
0. Earth leakage fault
1. No earth leakage fault
Digital input DIIL (as indicated by
status, bit 15).
Digital input DI1 (as indicated by
status, bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
status, bit 1).
Digital input DI3 (as indicated by
status, bit 2).
Note: DI3 is reserved for main breaker/contactor fault in
the control program. Do not select it for any other use.
Digital input DI4 (as indicated by
status, bit 3).
Note: DI4 is reserved for auxiliary circuit breaker fault in
the control program. Do not select it for any other use.
Digital input DI5 (as indicated by
status, bit 4).
Digital input DI6 (as indicated by
status
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input/output DIO2 (as indicated by
delayed
status, bit 1).
Source selection (see
Terms and abbreviations
39).
Selects how the diode supply unit reacts when an
external earth leakage is detected.
The diode supply unit generates a warning
earth
leakage.
The diode supply unit trips on a fault
leakage.
Defines the source for fault
fault.
0 = Fault
1 = No fault
Auxiliary circuit breaker fault
No auxiliary circuit breaker fault
Digital input DIIL (as indicated by
status, bit 15).
trials.
selection.
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
111.02 DIO
111.02 DIO
on page
AE87 Ext
2E08 Ext earth
5E13 Auxiliary circuit breaker
110.02 DI delayed
Parameters 99
Def/FbEq16
30
10 = 1 s
0.0 s
10 = 1 s
Inactive
(true)
0
1
2
3
4
5
6
7
8
11
12
-
Fault
0
1
DI4
0
1
2