Fault Functions - ABB ACS880 Firmware Manual

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

96 Parameters
No.
Name/Value
131

131 Fault functions

131.01
External event 1
source
Active (false)
Inactive (true)
DIIL
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
131.02
External event 1
type
Fault
Warning
Warning/Fault
131.03
External event 2
source
131.04
External event 2
type
Fault
Warning
Warning/Fault
131.05
External event 3
source
Description
Settings that define the behavior of the supply unit
upon fault situations.
Defines the source of external event 1. See also
parameter
131.02 External event 1
0
1
Digital input DIIL (as indicated by
status, bit 15).
Digital input DI1 (as indicated by
status, bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
status, bit 1).
Digital input DI3 (as indicated by
status, bit 2).
Note: DI3 is reserved for main breaker/contactor fault in
the control program. Do not select it for any other use.
Digital input DI4 (as indicated by
status, bit 3).
Note: DI4 is reserved for auxiliary circuit breaker fault in
the control program. Do not select it for any other use.
Digital input DI5 (as indicated by
status, bit 4).
Digital input DI6 (as indicated by
status
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input/output DIO2 (as indicated by
delayed
status, bit 1).
Source selection (see
Terms and abbreviations
39).
Selects the type of external event 1.
The external event generates a fault.
The external event generates a warning.
If the diode supply unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Defines the source of external event 2. See also
parameter
131.04 External event 2
For the selections, see parameter
source.
Selects the type of external event 2.
The external event generates a fault.
The external event generates a warning.
If the diode supply unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Defines the source of external event 3. See also
parameter
131.06 External event 3
For the selections, see parameter
source.
type.
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
111.02 DIO
111.02 DIO
on page
type.
131.01 External event 1
type.
131.01 External event 1
Def/FbEq16
Inactive
(true)
0
1
2
3
4
5
6
7
8
11
12
-
Fault
0
1
3
Inactive
(true)
Fault
0
1
3
Inactive
(true)

Advertisement