100 Parameters
No.
Name/Value
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
131.33
Cabinet
temperature fault
source
Active (false)
Inactive (true)
DIIL
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Description
Digital input DI1 (as indicated by
status, bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
status, bit 1).
Digital input DI3 (as indicated by
status, bit 2).
Note: DI3 is reserved for main breaker/contactor fault in
the control program. Do not select it for any other use.
Digital input DI4 (as indicated by
status, bit 3).
Note: DI4 is reserved for auxiliary circuit breaker fault in
the control program. Do not select it for any other use.
Digital input DI5 (as indicated by
status, bit 4).
Digital input DI6 (as indicated by
status
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input/output DIO2 (as indicated by
delayed
status, bit 1).
Source selection (see
Terms and abbreviations
39).
Activates/inactivates the monitoring for the cabinet
thermal switch, and defines the source for the
monitored signal. If the monitoring detects an
overtemperature, it trips the supply unit to fault
Cabinet temperature
fault.
Status of the monitored signal and implication:
1 = Temperature is normal -> no fault
0 = Overtemperature -> fault trip
Monitoring function is active.
Monitoring function is inactive.
Monitoring function is active and it reads the status
indication through DIIL
Monitoring function is active and it reads the status
indication through DI1
Monitoring function is active and it reads the status
indication through DI2
Monitoring function is active and it reads the status
indication through DI3
Monitoring function is active and it reads the status
indication through DI4
Monitoring function is active and it reads the status
indication through DI5
Monitoring function is active and it reads the status
indication through DI6
Monitoring function is active and it reads the status
indication through DIO1
0).
Monitoring function is active and it reads the status
indication through DIO2
1).
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
111.02 DIO
111.02 DIO
(110.02 DI delayed
status, bit 15).
(110.02 DI delayed
status, bit 0).
(110.02 DI delayed
status, bit 1).
(110.02 DI delayed
status, bit 2).
(110.02 DI delayed
status, bit 3).
(110.02 DI delayed
status, bit 4).
(110.02 DI delayed
status, bit 5).
(111.02 DIO delayed
status, bit
(111.02 DIO delayed
status, bit
Def/FbEq16
3
4
5
6
7
8
11
12
on page
-
DI1
4E06
0
1
2
3
4
5
6
7
8
11
12