196 Fieldbus control through a fieldbus adapter
Setting up the communication between DSU and inverter
unit
Connect the fiber optic cables between the DDCS communication port of the
inverter unit (parameter 60.71 INU-LSU communication port) and the DDCS
controller port of the DSU (parameter
In ACS880-07 drives, setting the DSU parameter
Yes automatically sets the following DSU parameters to their right values:
DSU parameter
120.01 Ext1 commands
120.02 Ext1 start trigger
120.12 Run enable 1
160.58 DDCS controller comm loss time
160.51 DDCS controller comm port
161.51 Data set 11 data 1 selection
162.51 Data set 10 data 1 selection
In ACS880-07 drives, setting the INU parameter 95.20 HW options word 1 bit 11 to
Yes automatically sets the following INU parameters to their right values:
Inverter unit parameter
60.71 INU-LSU communication port
94.01 LSU control
61.151 INU-LSU data set 10 data 1 sel
62.151 INU-LSU data set 11 data 1 sel
In the diode supply unit, data transmitted from the diode supply unit is defined with
parameters
161.51 Data set 11 data 1 selection...161.74 Data set 25 data 3
Data is received using parameters
set 24 data 3
selection.
In the inverter unit, data transmitted to the diode supply unit is defined with
parameters 61.151...61.186. Data is received using parameters 62.151...62.174.
With the settings above, the inverter unit controls the diode supply unit. In other
words, the diode supply unit receives the Control word from the inverter unit and
transmits the Status word to the inverter unit.
Note: The control program still requires the Run enable command from digital input
DI2 (by default) which is normally wired to the DSU door switch.
160.51 DDCS controller comm
195.20 HW options word 1
Setting
DDCS controller
Level
DI2
Set time, eg. 100 ms.
Set port to be used. Eg. RDCO CH0 is used with
the UCU control unit.
SW 16bit
CW 16bit
Setting
RDCO CH1
On
LSU CW
SW 16bit
162.51 Data set 10 data 1 selection...162.74 Data
port).
bit 11 to
selection.