ABB ACS880 Firmware Manual page 115

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
150.13
FBA A control word
00000000h ...
FFFFFFFFh
150.16
FBA A status word
00000000h ...
FFFFFFFFh
150.17
FBA A actual
value 1
-2147483648...
2147483647
150.18
FBA A actual
value 2
-2147483648...
2147483647
150.21
FBA A timelevel sel
Normal
Fast
Very fast
Monitoring
150.31
FBA B enable
Disable
Option slot 1
Option slot 2
Option slot 3
150.32
FBA B comm loss
func
Description
Displays the control word received from fieldbus
adapter A. For the commands assigned to each bit, see
chapter
Fieldbus control through a fieldbus
Control word received from fieldbus adapter A.
Displays the status word sent to fieldbus adapter A. For
the commands assigned to each bit, see chapter
Fieldbus control through a fieldbus
Status word sent to fieldbus adapter A.
Displays raw actual value ACT1 sent to fieldbus adapter
A.
Raw ACT1 sent to fieldbus adapter A.
Displays raw actual value ACT2 sent to fieldbus adapter
A.
Raw ACT2 sent to fieldbus adapter A.
Selects the communication speed for the fieldbus
adapter A.
In general, lower speeds reduce CPU load. The table
below shows the read/write intervals for cyclic and
acyclic data with each parameter setting.
Selection
Cyclic*
Monitoring
10 ms
Normal
2 ms
Fast
500 µs
Very fast
250 µs
*Cyclic data consists of fieldbus Control and Status
words, Act1 and Act2.
**Acyclic data consists of the parameter data mapped
to parameter groups
152 FBA A data in
data
out.
Normal speed.
Fast speed.
Very fast speed.
Low speed. Optimized for PC tool communication and
monitoring usage.
Enables/disables communication between the supply
unit and fieldbus adapter B, and specifies the slot the
adapter is installed into.
Communication between supply unit and fieldbus
adapter B disabled.
Communication between supply unit and fieldbus
adapter B enabled. The adapter is in slot 1.
Communication between supply unit and fieldbus
adapter B enabled. The adapter is in slot 2.
Communication between supply unit and fieldbus
adapter B enabled. The adapter is in slot 3.
Selects how the supply unit reacts upon a fieldbus
communication break. The time delay is defined by
parameter
150.33 FBA B comm loss
Parameters 115
Def/FbEq16
-
adapter.
1 = 1
-
adapter.
1 = 1
-
1 = 1
-
1 = 1
Normal
Acyclic**
10 ms
10 ms
2 ms
500 µs
and
153 FBA A
0
1
2
3
Disable
0
1
2
3
No action
timeout.