word,
190.75 LSU status word
selection of parameters cannot be changed by the user.
Other data loggers
User data logger
A custom data logger can be configured using the Drive composer pro PC tool. This
functionality enables the free selection of up to eight parameters to be sampled at
selectable intervals. The triggering conditions and the length of the monitoring
period can also be defined by the user within the limit of approximately 8000
samples. In addition to the PC tool, the status of the logger is shown by parameter
196.61 User data logger status
parameters
196.63 User data logger trigger
configuration, status and collected data is saved to the memory unit for later
analysis.
PSL2 data logger
The UCU control unit contains a data logger that collects data from the diode supply
modules to help fault tracing and analysis. The data is stored onto the microSDHC
memory card inserted into the UMU memory unit and can be analyzed by ABB service
personnel.
Parameters that contain warning/fault information
The codes of active warnings and faults (maximum five each), and five previously
occurred warnings and faults are stored in the parameters of group
and faults
(page 44).
1,
106.01 Main control
word. The triggering sources can be selected by
and
word,
110.01 DI
196.64 User data logger
Fault tracing 165
status. The
start). The
104 Warnings