ABB ACS880 Firmware Manual page 120

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

120 Parameters
No.
Name/Value
154.26
FBA B Par26
0...65535
154.27
FBA B par refresh
Done
Refresh
154.28
FBA B par table ver
154.29
FBA B drive type
code
0...65535
154.30
FBA B mapping file
ver
0...65535
154.31
D2FBA B comm
status
Idle
Exec.init
Time out
Conf.err
Off-line
On-line
Reset
154.32
FBA B comm SW
ver
154.33
FBA B appl SW ver
Description
See parameter
154.26 FBA B
Fieldbus adapter configuration parameter.
Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value
reverts automatically to Done.
Note: This parameter cannot be changed while the
diode supply unit is running.
Refreshing done.
Refreshing.
Displays the parameter table revision of the fieldbus
adapter module mapping file stored in the memory.
In format axyz, where a = major revision number; xy =
minor revision number; z = correction number.
Parameter table revision of adapter module.
Displays the type code of the fieldbus adapter module
mapping file stored in the memory.
Type code of fieldbus adapter module mapping file.
Displays the fieldbus adapter module mapping file
revision stored in the memory of the supply unit in
decimal format.
Example: Integer 263 -> 0x107 = revision 1.07
Mapping file revision.
Displays the status of the fieldbus adapter module
communication.
Adapter is not configured.
Adapter is initializing.
A time-out has occurred in the communication between
the adapter and the supply unit.
Adapter configuration error: the major or minor revision
code of the common program revision in the fieldbus
adapter module is not the revision required by the
module (see parameter
mapping file upload has failed more than three times.
Adapter is off-line.
Adapter is on-line.
Adapter is performing a hardware reset.
Displays the common program revision of the adapter
module in format axyz, where a = major revision number,
xy = minor revision number, z = correction number.
Example: 190A = revision 1.90A.
Common program revision of adapter module.
Displays the application program revision of the
adapter module in format axyz, where a = major revision
number, xy = minor revision number, z = correction
number or letter.
Example: 190A = revision 1.90A.
Application program version of adapter module.
Par2.
154.32 FBA B comm SW
Def/FbEq16
-
1 = 1
Done
0
1
-
1 = 1
-
1 = 1
-
1 = 1
Idle
0
1
2
3
ver), or
4
5
6
-
1 = 1
-
1 = 1

Advertisement

Table of Contents
loading

Table of Contents