ABB ACS880 Firmware Manual page 65

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
113.27
AO2 source min
-32768.0 ...
32767.0
113.28
AO2 source max
-32768.0 ...
32767.0
113.29
AO2 out at AO2 src
min
0.000 ... 22.000
mA
113.30
AO2 out at AO2 src
max
0.000 ... 22.000
mA
113.91
AO1 data storage
-327.68 ... 327.67
113.92
AO2 data storage
-327.68 ... 327.67
Description
Defines the real value of the signal (selected by
parameter
113.22 AO2
source) that corresponds to the
minimum AO2 output value (defined by
parameter
113.29 AO2 out at AO2 src
I
(mA)
AO2
113.30
113.29
113.27
I
(mA)
AO2
113.30
113.29
113.28
Real signal value corresponding to minimum AO2 output
value.
Defines the real value of the signal (selected by
parameter
113.22 AO2
source) that corresponds to the
maximum AO2 output value (defined by
parameter
113.30 AO2 out at AO2 src
parameter
113.27 AO2 source
Real signal value corresponding to maximum AO2
output value.
Defines the minimum output value for analog output
AO2.
See also drawing at parameter
Minimum AO2 output value.
Defines the maximum output value for analog output
AO2.
See also drawing at parameter
Maximum AO2 output value.
Storage parameter for controlling analog output AO1
eg. through fieldbus.
In
113.12 AO1
source, select
this parameter as the target of the incoming value data.
Storage parameter for AO1.
Storage parameter for controlling analog output AO2
eg. through fieldbus.
In
113.22 AO2
source, select
this parameter as the target of the incoming value data.
Storage parameter for AO2.
min).
113.28
Signal (real)
selected by par.
113.27
Signal (real)
selected by par.
max). See
min.
113.27 AO2 source
113.27 AO2 source
AO1 data
storage. Then set
AO2 data
storage. Then set
Parameters 65
Def/FbEq16
0.0
113.22
113.22
1 = 1
100.0
1 = 1
4.000 mA
min.
1000 = 1 mA
20.000 mA
min.
1000 = 1 mA
0.00
100 = 1
0.00
100 = 1

Advertisement

Table of Contents
loading

Table of Contents