ABB ACS880 Firmware Manual page 107

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
133.51
Value count 1 limit
-2147483008 ...
2147483008
133.52
Value count 1 func
Bit
0
1
2...15
0000h...FFFFh
133.53
Value count 1 src
Not selected
Other [bit]
133.54
Value count 1 div
0.001 ...
2147483.000
133.55
Value count 1 warn
sel
Value 1
133.60
Value count 2 act
-2147483008 ...
2147483008
133.61
Value count 2 limit
-2147483008 ...
2147483008
Description
Sets the warning limit for value counter 1.
Warning limit for value counter 1.
Configures value counter 1. The counter calculates its
actual value (133.53) by integrating the monitored value
(133.xx) with respect to time. A divisor may be applied to
the count (see
When the actual value exceeds the limit set by
parameter
133.51 Value count 1
specified by
133.55 Value count 1 warn sel
enabled by this parameter).
The signal is sampled at 1-second intervals. Note that
the scaled (see the "Def/FbEq16" column at the signal in
question) value is used.
The current value of the counter is readable from
parameter
133.50 Value count 1
Counter status
the limit.
Function
Counter mode
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds
1 = Saturate: If warning is enabled by bit 1, it stays active until reset
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning is given when the limit is reached
Reserved
Value counter 1 configuration word.
Selects the signal to be monitored by value counter 1.
None.
Source selection (see
39).
Divisor for value counter 1. The value of the monitored
signal is divided by this value before integration.
Divisor for value counter 1.
Selects the warning message for value counter 1.
AE49 Value counter
Reading of value counter 2. Can be reset from the Drive
composer PC tool, or from the control panel by keeping
Reset depressed for over 3 seconds.
Reading of value counter 2.
Sets the warning limit for value counter 2.
Warning limit for value counter 2.
133.54 Value count 1
div).
limit, the warning
act. Bit 4 of
indicates that the count has exceeded
Terms and abbreviations
1.
Parameters 107
Def/FbEq16
0
1 = 1
0000b
is given (if
133.01
1 = 1
Not selected
0
on page
-
1.000
1 = 1
Value 1
4
-
1 = 1
0
1 = 1