ABB ACS880 Firmware Manual page 136

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

136 Parameters
No.
Name/Value
196.29
Time sync source
status
Bit
Name
0
Time tick received
1
Aux Time tick
received
2
Tick interval is too
long
3
DDCS controller
4
Master/Follower
5
Reserved.
6
D2D
7
FbusA
8
FbusB
9
EFB
10
Ethernet
11
Panel link
12
Ethernet tool link
13
Parameter setting
14
RTC
15
Drive On-Time
0000h...FFFFh
196.51
Clear fault and
event logger
0...65535
196.61
User data logger
status word
Bit
Name
0
Running
1
Triggered 1 = The user data logger has been triggered. The bit is cleared when
2
Data
available
3
Configure
d
4...15 Reserved
0000b...1111b
Description
Time source status word.
This parameter is read-only.
Description
1 = 1st priority tick received: Tick has been received from 1st
priority source.
1 = 2nd priority tick received: Tick has been received from
2nd priority source.
1 = Yes: Tick interval too long (accuracy compromised).
1 = Tick received: Tick has been received from an external
controller.
1 = Tick received: Tick has been received through the
master/follower link.
1 = Tick received: Tick has been received through the drive-
to-drive link.
1 = Tick received: Tick has been received through fieldbus
interface A.
1 = Tick received: Tick has been received through fieldbus
interface B.
1 = Tick received: Tick has been received through the
embedded fieldbus interface.
1 = Tick received: Tick has been received through the
Ethernet port on control unit.
1 = Tick received: Tick has been received from the control
panel, or Drive composer PC tool connected to the control
panel.
1 = Tick received: Tick has been received from Drive
composer PC tool through an FENA-xx module.
1 = Tick received: Tick has been set by parameters
196.24...196.26.
1 = RTC time in use: Time and date have been read from the
real-time clock.
1 = Drive on-time in use: Time and date are displaying drive
on-time.
Time source status word 1.
Clears the contents of the event logs. See section
Warning/fault history and analysis
00001 = Clear the event logs. (The value will
automatically revert to 00000.)
Provides status information on the user data logger
(see page 165).
Description
1 = The user data logger is running. The bit is cleared after the post-
trigger time has passed.
the logger is restarted.
1 = The user data logger contains data that can be read. Note that the
bit is not cleared because the data is saved to the memory unit.
1 = The user data logger has been configured. Note that the bit is not
cleared because the configuration data is saved to the memory unit.
User data logger status word.
on page 164.
Def/FbEq16
-
1 = 1
-
1 = 1
0000b
1 = 1